User Manual of A90 Series Inverter
84
synchronous motor
F06.48
Filtering time
constant of speed
tracking of
synchronous motor
0.00~10.00
ms
0.40
○
F06.49
Speed tracking
control intensity of
synchronous motor
1.0~100.0
5.0
○
F06.50
Speed tracking
control threshold of
synchronous motor
0.00~10.00
0.20
○
F06.51
Injection current (Iq)
rise time of
synchronous motor
0.010~1.000
S
5.0
F07
Protection function setting group
F07.00 Protection shield
E20 E22 E13 E06 E05 E04
E0
7
E08
000
00000
○
0: valid protection
1: shielded protection
F07.01
Motor overload
protection gain
0.20~10.00
1.00
●
F07.02
Motor overload
pre-alarm coefficient
50~100
%
80
●
F07.06
Bus voltage control
options
Ones place: Instantaneous
stop/no-stop function options
0: Invalid
1: deceleration
2: deceleration to stop
Tens place: Overvoltage stall
function options
0: Invalid
1: valid
10
○
F07.07
Voltage of
overvoltage stall
control
110.0~150.0 (380V,100.0=537V)
%
131.0
(703V)
○
F07.08
Instantaneous
stop/no-stop
operating voltage
60.0 to instantaneous stop/no-stop
recovery voltage (100.0 =
standard bus voltage)
%
76.0
○
F07.09
Instantaneous
stop/no-stop recovery
voltage
Instantaneous stop/no-stop
operating voltage to 100.0
%
86.0
●
F07.10
Check time for
instantaneous
0.00-100.00
s
0.50
●