User Manual of A90 Series Inverter
188
Function code Function code name Parameter description
Unit
Default
setting
Attribute
F07.28
Stall fault detection
time
0.0-6000.0 (0.0: no stall fault
detection)
s
0.0
○
F07.29
Stall control
intensity
0 - 100
%
100
○
When the continuous stall time exceeds the set value of F07.28, the driver will report a
stall fault.
In the stall status, the driver will perform automatic control according to the set value
of F07.29. The intensity setting depends on the on-site application, instead of
maximization.
7.9
Multi-segment Speed and Simple PLC Parameter Group of F08
Group
Function
code
Function code
name
Parameter description
Unit
Default
setting
Attribute
F08.00
Multi-segment
speed 1
0.00 to maximum frequency
F00.16
Hz
0.00
●
F08.01
Multi-segment
speed 2
0.00 to maximum frequency
F00.16
Hz
5.00
●
F08.02
Multi-segment
speed 3
0.00 to maximum frequency
F00.16
Hz
10.00
●
F08.03
Multi-segment
speed 4
0.00 to maximum frequency
F00.16
Hz
15.00
●
F08.04
Multi-segment
speed 5
0.00 to maximum frequency
F00.16
Hz
20.00
●
F08.05
Multi-segment
speed 6
0.00 to maximum frequency
F00.16
Hz
25.00
●
F08.06
Multi-segment
speed 7
0.00 to maximum frequency
F00.16
Hz
30.00
●
F08.07
Multi-segment
speed 8
0.00 to maximum frequency
F00.16
Hz
35.00
●
F08.08
Multi-segment
speed 9
0.00 to maximum frequency
F00.16
Hz
40.00
●
F08.09
Multi- speed 10
0.00 to maximum frequency
F00.16
Hz
45.00
●
F08.10
Multi-segment
speed 11
0.00 to maximum frequency
F00.16
Hz
50.00
●
F08.11
Multi-segment
speed 12
0.00 to maximum frequency
F00.16
Hz
50.00
●