Motor 1 parameter group of F01 group
Function
code
Function code name
Parameter description
Unit
Default
setting
Attribute
F01.00 Motor type
0: ordinary asynchronous
motor
1: variable-frequency
asynchronous motor
2: permanent magnet
synchronous motor
0
○
The A90 series inverter supports asynchronous and synchronous motors. Please set this
parameter correctly according to the actual situation.
Function
code
Function code
name
Parameter description
Unit Default setting Attribute
F01.01
Rated power of
electric motor
0.10~650.00
kW
Depending on the
motor type
○
F01.02
Rated voltage of
motor
50~2000
V
Depending on the
motor type
○
F01.03
Rated current of
motor
0.01 ~ 600.00 (rated power
of motor: ≤ 75 kW)
0.1 ~ 6000.0 (rated power of
motor: > 75 kW)
A
Depending on the
motor type
○
F01.04
Rated frequency
of motor
0.01~600.00
Hz
Depending on the
motor type
○
F01.05 Rated speed
1~60000
rpm
Depending on the
motor type
○
F01.06
Motor winding
connection
0: Y
1: Δ
Depending on the
motor type
○
F01.07
Rated power
factor of motor
0.600~1.000
Depending on the
motor type
○
F01.08 Motor efficiency 30.0~100.0
%
Depending on the
motor type
○
The above function codes are the nameplate parameters of the asynchronous motor.
When the motor is connected to the inverter for the first time, regardless of VF control or
vector control, the above parameters must be correctly set according to the motor nameplate
before operation.
When the rated power (F01.01) of the motor is changed, the values of F01.03 to
F01.08 of the inverter will change automatically. Pay attention to this during operation.