124
5.25
F6 Troubleshooting
Digital display output
Description
1F6 indicates A system buss voltage error (PTC).
2F6 indicates B system buss voltage error (PTC).
Only occurred in standby status.
Error code is displayed on main PCB and user interface.
Possible causes
Abnormal power supply voltage
Loosened wiring within electric control box
High voltage circuit error
AC filter board damaged
3-pahse bridge rectifier damaged
Compressor Inverter module damaged
Procedure
Refer to P6 protection troubleshooting: xL1 and xL2.