Ambiguity function in combustible gas detector smart sensors
In compliance with applicable standards, the ambiguity function is activated when a detected
gas concentration rises above 120% LEL. The signal is locked at 21.7 mA to protect against
any false measurement due to oxygen deficiency.
This function also cuts the power to the cartridge to avoid damaging the sensitive element.
The measurement signal can only be unlocked by the operator using the TLU600
remote control unit. Before that, the non-presence of inflammable gas or vapour
in atmosphere must be control by the user.
Even switching the power off and power on again from the control room will not
unlock the signal.
The TLU displays the following screen:
To clear the ambiguity, follow the instruction below with the TLU600:
INFO / STAT / ALRM / ACK. (YES)
The device then goes in warm-up mode (refer to §6.3) for 90s. The detector is in inhibition
mode. The current output and the default relay (if factory configuration) are consequently
activated.
A warming-up timer starts to countdown from 90 sec.
Then, the inhibition is released.
Содержание DM-TT6-K
Страница 9: ...MultiXplo MultiTox Page 9 60 NOSP15759 Rev 10 Figure 1 Layout Drawing Congestion see Figure 2...
Страница 32: ...MultiXplo MultiTox Page 32 60 NOSP15759 Rev 10...
Страница 48: ...MultiXplo MultiTox Page 48 60 NOSP15759 Rev 10...
Страница 56: ...MultiXplo MultiTox Page 56 60 NOSP15759 Rev 10 10 CONFORMITY CERTIFICATE...
Страница 57: ...MultiXplo MultiTox Page 57 60 NOSP15759 Rev 10...
Страница 58: ...MultiXplo MultiTox Page 58 60 NOSP15759 Rev 10...
Страница 59: ...MultiXplo MultiTox Page 59 60 NOSP15759 Rev 10...