Saving IDNet and IDNAC Test Results
IDNet and IDNAC test results can be saved to one of the 60 memory slots.
Each slot can be tagged with a 20-character name for easy recall at a later
time. To save test results, select Save Channel Data from the main menu.
The first available memory slot will be displayed.
The second line on the LCD contains a 20-
character, user editable name for the data
being saved. The cursor (underline
character) is under the first letter of the
name. To enter a new name, use the
or
keys to change the character and the left/
right arrow keys to move the cursor.
Pressing the F2 key clears the remainder of the line from the cursor position
to the end (including the character at the cursor). If you want to save the
results to a different channel, press the F1 key. Brackets will surround the slot
number and the
or
keys are used to select the desired slot number (1-
60). Press ENT to save to this new slot. Note that the TSIT allows you to
override a previously filled memory slot using this method.
Recalling Test Results
Previously saved tests are recalled for review by selecting Recall Saved
Data from the main menu. Use the
or
keys to select the memory slot to
recall then press ENT. The contents of this memory slot are loaded into main
memory for review.
Upload to PC
Once IDNet and IDNAC test data is
saved to one of the memory slots, it
may be uploaded to the TrueSTART
Analyzer PC software for review. Attach
the download harness, 733-794, to the
connector on the back of the TSIT.
Orient the connector so that the striped
edge is on the left. The other end of the
cable is a DB9 connector, which
attaches to an RS232 port on your PC.
A USB to RS232 adapter is provided in case the PC does not have RS232
ports.
ENT
Save Results
Memory Slot 06
F1 EDIT, ENT SAVE
Channel 06