General wiring 
precautions

All wiring 

must 

be copper conductors only.

Do not exceed the maximum wiring lengths specified in the wire length tables in this 
document.

If shielding is used: 
- Maintain the metallic continuity of the shield throughout the entire length of cable.

- The entire length of the cable must have a resistance greater than 1 X 10

6

 Ohms to earth 

ground.
- Ensure the shield is connected to a SHIELD terminal at each annunciator, and is 
terminated only at the main panel.

Ensure underground wiring is free of water.

Do not run wires through elevator shafts.

Wire runs in plenums must be in a conduit unless they are rated for plenum use.

Splicing is permitted in the following situations:
- All connections are soldered (rosin-core solder), crimped in metal sleeves, or 
encapsulated with an epoxy resin.
- When using solder or crimped metal sleeves, ensure the junction is insulated with a high 
grade electrical tape that equals the quality of the original insulating jacket.
- The continuity of the shield is maintained throughout the length of the cable.

Do not run other wiring in the same conduit as system wiring.

Specific wiring 
precaution

Ensure 24V power wiring is power limited.

Communication wiring is supervised and power limited.

4606-9102 LCD Annunciator wiring that leaves the building, above or below ground, 
requires overvoltage suppression at both ends for the communication and the power 
wiring. Communication and power wiring must meet the following requirements using:
- A Simplex Model 2081-9044 overvoltage protector (200 mA) or a Simplex Model 
2081-9027 (200 mA) isolated loop circuits protector.
- Simplex Model 2081-9028 (5-amp) isolated loop circuit protector.
- For underground wiring, select the appropriate isolated loop circuit protector. Run the 
circuit wiring in a separate parallel wiring trough, to separate it from any commercial 
power distribution wiring.
- For overhead wiring, select the appropriate isolated loop circuit protector. The wiring is 
limited to one contiguous property and the total wire length 

must 

not exceed 2500 feet 

(762 meters). Run the circuit wiring on separate poles, to separate it from any poles 
supporting commercial power distribution wiring. Run the wiring in parallel with direct 
relation to the commercial power distribution. The separation is a minimum distance, 
whichever is greater, of 100 feet (30.48 meters), or the maximum span between any two 
adjacent poles of either the system’s circuit or the commercial power distribution circuit.

For the maximum wire lengths with or without circuit protectors, see Tables 3 through 6.

Wire length 
tables

Table 3 and Table 4 show the maximum wire lengths possible for the power wiring. Table 5 

and Table 6 show the maximum wire lengths for the communication wiring.

Note: 

When using multiple annunciators and runs

ensure the total of all runs does not exceed 10,000 feet 

(3048 meters), including T-Taps.

The maximum number of 2081-9044 over-voltage protectors on a single communication loop is four. 

The maximum number of 2081-9028 isolated loop circuit protectors on a single communication loop is 

four.

Continued on the next page.

4606-9102 LCD Annunciator installation instructions

Содержание 4606-9102

Страница 1: ...ssociated equipment Product operation and reliability depend upon proper installation DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product inspect the contents of the carton for shipping damage If damage is apparent immediately file a claim with the carrier and notify an authorized Simplex product supplier ELECTRICAL HAZARD Disconnect electrical field power w...

Страница 2: ...COMM and power lines as shown in Figure 2 Figure 2 Terminating the COMM and Power Lines 2 Connect the ground harness to earth ground Note To prevent Electrostatic Discharge ESD use a wrist strap assembly that connects to ground Ensure the power is OFF before installing or servicing the annunciator Table 1 Power requirements and environmental limitations Voltage 24VDC Power Supply 24VDC Nominal 18V...

Страница 3: ...h SW2 8 sets the annunciator s baud rate SW2 8 OFF or OPEN 1200 Baud SW2 8 ON or CLOSED 9600 Baud Figure 4 DIP switch SW2 Continued on the next page 24C 0V 24VDC 24C 0V 24VDC TB1 TB2 COMM RUI COMM RUI SHIELD SHIELD COMM RUI COMM RUI GROUND HARNESS 733 936 ON Note DIP switch SW2 is located at the bottom of the electronics assembly Position of 3 shown in OFF position Example depicts Address 4 Baud R...

Страница 4: ...N ON ADDRESS 30 OFF OFF OFF OFF OFF ON ON ADDRESS 31 ON ON ON ON ON OFF ON ADDRESS 32 OFF ON ON ON ON OFF ON ADDRESS 33 ON OFF ON ON ON OFF ON ADDRESS 34 OFF OFF ON ON ON OFF ON ADDRESS 35 ON ON OFF ON ON OFF ON ADDRESS 36 OFF ON OFF ON ON OFF ON ADDRESS 37 ON OFF OFF ON ON OFF ON ADDRESS 38 OFF OFF OFF ON ON OFF ON ADDRESS 39 ON ON ON OFF ON OFF ON ADDRESS 40 OFF ON ON OFF ON OFF ON ADDRESS 41 ON...

Страница 5: ...ON ON OFF OFF OFF ON OFF ADDRESS 92 OFF ON OFF OFF OFF ON OFF ADDRESS 93 ON OFF OFF OFF OFF ON OFF ADDRESS 94 OFF OFF OFF OFF OFF ON OFF ADDRESS 95 ON ON ON ON ON OFF OFF ADDRESS 96 OFF ON ON ON ON OFF OFF ADDRESS 97 ON OFF ON ON ON OFF OFF ADDRESS 98 OFF OFF ON ON ON OFF OFF ADDRESS 99 ON ON OFF ON ON OFF OFF ADDRESS 100 OFF ON OFF ON ON OFF OFF ADDRESS 101 ON OFF OFF ON ON OFF OFF ADDRESS 102 OF...

Страница 6: ...ure 5 using a small screw driver Turn the potentiometer and observe the LCD display until the contrast is at the correct setting 6 Label the user defined labels appropriately Pull the top of the label pocket forward and insert the user defined labels 7 Using the four oval head screws provided mount the trim plate to the back box see Figure 6 Figure 6 Expanded view of 4606 9102 LCD Annunciator Cont...

Страница 7: ...using A Simplex Model 2081 9044 overvoltage protector 200 mA or a Simplex Model 2081 9027 200 mA isolated loop circuits protector Simplex Model 2081 9028 5 amp isolated loop circuit protector For underground wiring select the appropriate isolated loop circuit protector Run the circuit wiring in a separate parallel wiring trough to separate it from any commercial power distribution wiring For overh...

Страница 8: ...9ft 715 97m 0 200 2 500ft 762m 2 500ft 762m 1 482ft 451 71m 1 175ft 358 14m 0 300 2 500ft 762m 1 980ft 603 5m 988ft 301 14m 783ft 238 65m 0 400 2 361ft 719 63m 1 485ft 452 62m 741ft 225 85m 587ft 178 91m 0 500 1 889ft 575 76m 1 188ft 362 1m 593ft 180 74m 470ft 143 25m 0 600 1 574ft 479 75m 990ft 301 75m 494ft 150 57m 392ft 119 48m 0 700 1 349ft 411 17m 849ft 258 77m 423ft 128 93m 336ft 102 41m 0 8...

Отзывы: