9-11
4007ES Panel Programmer Manual (
579-1167)
Custom Control,
Continued
Specifying Floor
Names
The Floor drop-down list box contains an entry for all floors (i.e., if you set number of floors to
10 in the previous screen, there are 10 entries). To enter a floor's name, first click on the
drop-down list box to select the floor and then enter a descriptive label in the Floor Label text
box. Enter any comments in the Comment box at the bottom of the dialog.
.
Figure 9-16. Specify Floor Names
Specifying Input
and Static Points
Enter information for the other fields in this screen as follows:
• Alarm Points. Identifies the floor's input points (such as, detectors, pull stations).
• Non-Audio Points. Identifies the floor's non-audio (horns, strobes) notification points.
• Air ON Points. Identifies the pressurization fan and damper ON points.
• Exhaust ON Points. Identifies the exhaust fan and damper ON points.
• Air OFF Points. Identifies the pressurization fan and damper OFF points.
• Exhaust OFF Points. Identifies the exhaust fan and damper OFF points.
For each of these selections, when you click on the button, a taglist appears, with which you
can select specific points. Press the space bar to select a point. A “>>” symbol appears to the
left of the point to indicate that it is selected.
.
Figure 9-17. Input and Static Points
Note:
The user list is created starting from the first available user list and the number of list used depends
on the chosen configuration.
Click
Next
. A dialog containing the Custom Control equations generated by the wizard
appears. Click
Finish
.
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......