13-10
4007ES Panel Programmer Manual (
579-1167)
Adding or Editing Network Information,
Continued
Programming
Central Network
Reset
11. Click on the
Filter
icon at the top of the
Tag List
. When the list of choices appears, click on
the
Network Externals
check box. All of the External Points appear.
12. Click on the entry for
P211
and press the space bar.
13. Repeat Steps 10 through 12 for every node on the network.
Programming
Distributed
Network Reset
With Distributed Network Reset, the following occurs:
• Each node controls its own General Alarm Points.
• System Reset can be initiated from any node and all other nodes may also experience the
reset operation.
• System Points involved: P212 Detector/System Reset, and 105 External Entire System Reset
Points.
Figure 13-10. Distributed Network Reset
To configure Distributed Network Silence, do the following on each node.
1. Open the network job, using the network programmer.Open the job for one of the nodes.
2. When the ES Panel programmer appears, click on the
Network
tab at the top of the
programmer. When the Network window appears, click on the
Network Points
subtab at the
bottom of the Network window.
3. Right click in the Network window. When the choices appear, click on
Edit Externals.
A
dialog similar to the following appears. Click on the drop down list box and choose one of
the nodes on the network.
Figure 13-11. Choose Node
4. Click
OK
to close the dialog. When you do this, a tag list containing the public points from
the selected node appears. Click on
P212
and press the space bar to select the point. Click
OK
to close the taglist.
Continued on next page
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......