13-8
4007ES Panel Programmer Manual (
579-1167)
Adding or Editing Network Information,
Continued
Programming
Central Network
Silence
4. Click
OK
to close the dialog. When you do this, a tag list containing the public points from
the selected node appears. Click on
P217 Network Signal Silence
and press the space bar to
select the point. Click
OK
to close the taglist.
5. Repeat Steps 3 and 4 for every node on the network.
6. Click on the
List
tab at the top of the programmer. When the List window appears, click on
the
General List
subtab at the bottom of the window. Scroll through the list, right click on
L106 - External Alarm Silence Points
and select
Tag List
.
7. Click on the
Filter
icon at the top of the Tag List. When the list of choices appears, click on
the
Network Externals
check box. Click on the OK button. All of the External Points
appear.
8. Click on each entry for
P217 - Network Signal Silence
(each node on the network should
have an entry) and press the space bar to add the entry to L106. N:P217 represents the Node
Number.
Programming
Distributed
Network Silence
This setup allows a Network Silence to be initiated from any node on the network. The figure
below provides an overview of Distributed Network Silence. In this figure, each node's P217
pseudo has been declared external on the other nodes and L106 on each node has been edited to
include the external points.
Figure 13-8. Distributed Network Silence
To configure Distributed Network Silence, follow the steps in section “Programming Central
Network Silence” of this chapter for each node. Repeat Steps 3 through 7 for every node on the
network.
Содержание 4007ES Panels
Страница 1: ...4007ES and 4007ES Hybrid Fire Alarm Systems Programmer s Manual 579 1167 Rev D...
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 18: ......
Страница 36: ......
Страница 56: ......
Страница 122: ...9 38...
Страница 132: ......
Страница 134: ......
Страница 150: ......
Страница 166: ...A 16...
Страница 167: ......