7.3.3.
”HOLd” menu
This menu contains parameters connected with peak detection function. See also full
description of the peak detection function in paragraph:
DETECTION OF THE PEAK VALUES
“modE”
- the type of detected changes of the input signal, can be set to values:
”norm”
- peaks
, peak and next drop of the input signal of value equal at least
“PEA”
,
”inv”
- drops, drop and next peak of the input signal of value equal at least
“PEA”
,
“PEA”
- minimal detected signal change classified as peak or drop (see Figure 6.3)
“timE”
- maximum time of displaying of the peak (drop) value, can be set from 0.1 to 19.9
sec, with 0.1 sec. resolution
“HdiS”
- type of displayed values:
”rEAL”
- current value is displayed,
”HOLd”
- peak (drop) value is displayed,
7.3.4.
”Scod” parameter
This parameter defines user password (4-digits number). If this parameter is set at value
“0000”
, user password is turned off.
If the user do not remember his password, the access to the menu is possible
by the “one-use password”. To get this password please contact with
Marketing Division. “Single use password” can be used only one time, after
that it is destroyed. Entering this password causes in clearing of user
password, it means sets the user password to „0000”.
The “one-use password” can be used
ONE TIME ONLY
, it is impossible to use it
again! The “one-use password” can be restored by Service Division only.
7.3.5.
”rS” menu
This menu is connected with RS-485 interface, and sets his properties:
”Addr”
- this parameter defines the address of the device, accordingly to Modbus protocol.
It can be set in range from 0 to 199. If the value 0 is set then device, responds to
frames with address 255 (FFh).
”bAud”
- this parameter determines RS-485 interface baud rate. It can be set to one of 8
possible values:
”1.2”
,
”2.4”
,
”4.8”,
”9.6”
,
”19.2”
,
”38.4”
,
”57.6”
,
”115.2”
, which
respond to the baud rates of 1200, 2400, 4800, 9600, 19200, 38400, 57600 and
115200 bit/s respectively.