User manual - GALVANIC SEPARATOR SGS-61 

4.3.1. 

 

     4.3.1 

 

 Calculation of max. permissible  load resistance

 

 

Calculation of load resistance 

R

0

 

has been made using circuit from  Figure 4.5., following 

signatures has been assumed:

U

i

- minimal current output supply voltage assuring its proper operation,

I

max.

- maximal current measured in current loop (20 mA),

U

s

  - external power supply voltage (24V).

R

0

max.

=

U

s

U

i

I

max.

Values 

 

U

i

 = 9V,    

I

max.

 

= 20 mA  and  

U

= 24V 

gives:

         

R

0

max.

=

24

9

0,02

=

750

4.4. 

 

     MAINTENANCE

 

 

The unit does not have any internal replaceable components available to the user. Pay  

attention to the ambient temperature in the room where the unit is operating. Excessively high  

temperatures cause faster ageing of the internal components and shorten the fault-free time of  

unit operation. 

In cases where the unit gets dirty do not clean with solvents. For cleaning use warm water with  

small amount of detergent or in the case of more significant contamination ethyl or isopropyl  

alcohol. 

Using any other agents can cause permanent damage to the housing.

Product marked with this symbol should not be placed in municipal waste. Please  

check local regulations for disposal and electronic products.

10

Содержание SGC-61

Страница 1: ...l GALVANIC SEPARATOR SGS 61 Input type 4 20 mA Supply from current loop Read the user s manual carefully before starting to use the unit or software Producer reserves the right to implement changes wi...

Страница 2: ...SIGNAL ADJUSTMENT 11 Explanation of symbols used in the manual This symbol denotes especially important guidelines concerning the installation and operation of the device Not complying with the guidel...

Страница 3: ...tage and interference filters Do not attempt to disassemble repair or modify the unit yourself The unit has no user serviceable parts Defective units must be disconnected and submitted for repairs at...

Страница 4: ...bility 0 05 C Bandwith 3dB 200 Hz Protection level IP 20 Housing type Housing dimensions DIN rail mounted 35 mm rail 80 x 6 1 x 93 8 mm Weight 35 g Operating temperature depending on version 0 C to 50...

Страница 5: ...on should be conducted by qualified personnel Read the basic safety requirements on page 3 prior to starting the installation All installation works must be conducted with a disconnected power supply...

Страница 6: ...EMBLY Disconnect the power supply prior to starting assembly Check the correctness of the performed connections prior to switching the unit on Figure 4 1 Housing dimensions Figure 4 2 Method of mounti...

Страница 7: ...stallation according to this manual local safety and EMC regulations Wiring must meet appropriate standards and local regulations and laws Tighten the clamping screws The recommended tightening torque...

Страница 8: ...netically induced interference the use of twisted couples of signal cables so called spirals is recommended The spiral best if shielded must be used with RS 485 serial transmission connections Figure...

Страница 9: ...mple of device connection Signal polarization on input connectors IN IN is fixed Signal polarization on output connectors OUT1 OUT2 is free 9 4 5 1 power supply 24V two wire transducer R0 power supply...

Страница 10: ...es not have any internal replaceable components available to the user Pay attention to the ambient temperature in the room where the unit is operating Excessively high temperatures cause faster ageing...

Страница 11: ...ment output current are available Figure 5 1 Potentiometers location Potentiometers description P1 output current adjustment at IIN 4 00 mA P2 output current adjustment at IIN 20 00 mA After regulatio...

Страница 12: ...SIMEX Sp z o o ul Wielopole 7 80 556 Gda sk Poland tel 48 58 762 07 77 fax 48 58 762 07 70 http www simex pl e mail info simex pl...

Отзывы: