background image

Chiller and Inverter Air/Water heat pumps with axial fan

User-Installer Manual

SHP M PLUS

Models

021 - 026 - 028 - 032

Fonderie SIME S.p.A.  

 

 

 

 

 

 

 

 

6332358 – 02/2022 – R4

----------------------------------------------------------------------------------------------------------------------------------------------

This manual has been created for informative purpose. The company declines any responsibility for the results of any projecting or any installation based on the explanations 

and/or on the technical specifications provided in this manual. It is besides forbidden the reproduction under any form of the texts and of the figures contained in this manual.

"This manual is a translation from the official italian language version. For reasons of environmental respect the Company will not provide the hard copy in the original language 

which could be directly requested or downloaded from the Company website at any time. In case of any dispute, the original language manual will be the trusted one".

Содержание SHP M PLUS 021

Страница 1: ...tions and or on the technical specifications provided in this manual It is besides forbidden the reproduction under any form of the texts and of the figures contained in this manual This manual is a t...

Страница 2: ...bsorbed power heat pump fans 0121 0126 correct sound power reference to the standard UNI EN ISO 9641 1 02 10 2021 EM AR 0121 0126 data update for fan change heat pumps condition A7W45 size 0121 and co...

Страница 3: ...3 LIFTING AND HANDLING 11 5 3 1 Lifting mode 11 5 4 POSITIONING AND MINIMUM TECHNICAL CLEARANCES 12 5 5 DIMENSIONS 14 5 5 1 Model SHP M PLUS 0121 SHP M PLUS 0126 14 5 5 2 Model SHP M PLUS 0128 SHP M P...

Страница 4: ...TENCE 29 10 DECOMMISSIONING 29 11 RESIDUAL RISK 30 12 TECHNICAL DATA 34 12 1 TECHNICAL SHEET i 32V5C MIDI 34 12 2 TECHNICAL SHEET SHP M PLUS 35 12 3 UNIT AND AUXILIARY ELECTRICAL DATA 37 13 OPERATING...

Страница 5: ...herefore make sure to use the supplied manual for the installed unit The user is recommended to follow the instructions contained in this booklet especially those concerning safety and routine mainten...

Страница 6: ...sensory or mental capabilities or without experience or the necessary knowledge as long as they are supervised or after they themselves have received instructions on the safe use of the appliance and...

Страница 7: ...gn phase the indications contained in UNI EN ISO 14738 regarding workstations on the machinery were followed and the lifting limits imposed by UNI ISO 11228 1 were evaluated Make sure to maintain duri...

Страница 8: ...faces Clothes that can become entan gled or sucked in by air flows should be avoided Wear safety shoes with non slip soles especially in rooms with slippery floor Gloves During maintenance or cleaning...

Страница 9: ...s Allow e cient air exchange and or suc on the work environments Advice for safe use Do not breath in fumes or aerosol Storage Close carefully and store in a cool dry and well ven lated area Keep in o...

Страница 10: ...ources near the unit No smoking is allowed near the unit Transport and storage must be performed in accordance with the national regulations in force Specifically according to ADR provisions the total...

Страница 11: ...ry sharp and can cause serious injuries After the maintenance operations close the panels by fixing them with screws 5 2 TRANSPORT AND STORAGE LIMIT TEMPERATURE Minimum storage temperature C 10 C Maxi...

Страница 12: ...t installation place must be free from foliage dust etc which could clog or cover the coil Installation in areas subject to water stagnation or fall for example from gutters should be avoided Also avo...

Страница 13: ...refer to the classification of the area according to the Beaufort table If the value is 7 strong wind average wind speed 13 9 17 1 m s it is strictly necessary to keep the fan always powered thus prev...

Страница 14: ...ical data and the sound emission limits based on the installation area of the unit with reference to the DPCM of 14 11 1997 An assessment must also be made if the unit is installed in the proximity of...

Страница 15: ...t 5 6 CENTRE OF GRAVITY AND DAMPERS LOCATION In the following tables we report the position of the centre of gravity of each machine with reference to the dimensions shown in the image P1 P2 P3 P4 A B...

Страница 16: ...plumbing connections must be made in accordance with national and or local regulations pipes can be made of steel galvanised steel or PVC Pipes must be accurately sized according to the nominal water...

Страница 17: ...dirt separator are missing from the unit the guarantee will be void Refer to the wiring diagram attached to the unit to connect the flow switch Never jumper connections of the flow switch in the term...

Страница 18: ...in an appropriate conveyor discharge Otherwise the discharged water could stagnate around the unit and become a source of danger due to slipping falling 5 8 3 Drainage system The units all of them ad...

Страница 19: ...B A If the unit must be completely drained first close the manual inlet and outlet shutters not supplied and then disconnect the pipes on the water inlet and outlet so that the liquid in the unit can...

Страница 20: ...l panel is connected to the chiller by 4 cables with a cross section of 1 5 mm2 The power cables must be separate from the remote control cables Maximum distance 50 metres CAUTION The remote control p...

Страница 21: ...ould give rise to untimely trips The following table shows the recommended cable sections for a maximum length of 30 m In any case depending on type of installation the location and the length of the...

Страница 22: ...istives 1 A inductives XP 8 1 8 2 Double set point valve outlet VDS1 Changeover contact single phase voltage 230Vac 50Hz 5A resistives 1 A inductives XP 4 1 4 2 System remote resistance output Changeo...

Страница 23: ...ves XP 10 1 10 2 Defrost indication Changeover contact single phase voltage 230Vac 50Hz 5A resistives 1 A inductives X12 1 X12 2 X12 1 X12 2 N L N L XLF 1 XNF 1 XLF 1 XNF 1 XNF 3 XLF 2 XNF 2 XLF 3 XNF...

Страница 24: ...ATE EVAPORATOR EXCHANGE PED TR 1 LOW PRESSURE TRANSDUCER EEV 1 ELECTRONIC EXPANSION VALVE PSH 1 HIGH PRESSURE SWITCH SV CHARGING ATTACHMENT HKA 1 HEAT EXCHANGER ANTIFREEZE RESISTOR F 1 FILTER DRIER TE...

Страница 25: ...YPASS LINE SOLENOIDE VALVE SV CHARGING ATTACHMENT SG 1 MOISTURE LIQUD INDICATOR F 1 FILTER DRIER PEH TC 1 HIGH PRESSURE TRANSDUCER HC 1 CRANKCASE RESISTENCE PED TR 1 LOW PRESSURE TRANSDUCER AF 1 AXIAL...

Страница 26: ...g seasonal stops etc Furthermore power is missing the crankcase heaters will not be powered with the risk of breaking the compressors when the unit is switched on CAUTION Do not modify the electrical...

Страница 27: ...sing internal parts make sure you have disconnected power CAUTION Before starting to operate safety checks must be performed to ensure the combustion hazard is reduced to the minimum The work must be...

Страница 28: ...l refrigerant leaks M x Check the operating pressure superheating and sub cooling R x Circulation pump efficiency R x If the unit is to be out of service for a long period drain the water from the pip...

Страница 29: ...rks may involve the replacement of broken components which may have significant mass Below is the list of components standard and optional and the approximate weight for each piece take into considera...

Страница 30: ...rushing caused by the possible instability of the unit during handling The procedures for correct unit handling and installation are indicated on the user installer manual under chapter 5 with in dica...

Страница 31: ...ndicated in the user in staller manual under chapter 5 In case of maintenance the use of the necessary personal protective equipment is recommended The possibility of triggering can not be eliminated...

Страница 32: ...sal are given in the user install er manual under chapter 10 Failure to comply with the in structions given in the manual Ergonomic fatigue musculoskel etal disorders caused by exertion during mainten...

Страница 33: ...to use an independent cable duct in order to remove the possibility of inter action with other devices Failure to comply with the recommendations regarding the electrical system X Generated by unit u...

Страница 34: ...eat exchanger Type of internal heat exchanger A piastre N internal heat exchangers 1 1 1 1 Water content L 1 7 1 7 2 1 2 1 Hydraulic circuit Useful head 1 kPa 79 1 55 8 66 3 50 2 Water content of hydr...

Страница 35: ...water temperature 30 35 C 7 Indicative data subject to changes For the correct value always refer to the technical label on the unit 8 Calculated for a decrease in system water temperature of 10 C wi...

Страница 36: ...W68S or equiv FW68S or equiv Refrigerant oil quantity L 1 5 1 5 1 5 1 5 Refrigerant circuits 1 1 1 1 Refrigerant Type R32 R32 R32 R32 Refrigerant charge 7 kg 4 3 4 3 5 1 5 1 Amount of refrigerant in e...

Страница 37: ...tch water flow rate l s 0 477 0 477 0 588 0 588 When the flow rate drops below the indicated limit flow switch minimum water flow rate the flow switch issues an alarm which may be reset only upon reac...

Страница 38: ...itioning and domestic hot water production HEAT PUMP MODE 15 20 25 30 35 40 45 50 55 60 65 25 20 15 10 5 0 5 10 15 20 25 30 35 40 Tw C Ta C A Tw water temperature Ta air temperature A the maximum Hz f...

Страница 39: ...ons identifying operation of the unit as shown in the table below Cooling mode led led ON if unit is in COOL or COOL SAN mode Heating mode led led ON if unit is in HEAT or HEAT SAN mode Pump led led O...

Страница 40: ...MENU The following are the main features for navigating the menus especially describing functions which are not obvious The main menu has the following items MEN LABEL LEVEL PASSWORD OTHER CONDITIONS...

Страница 41: ...ncrease in discharge pressure Low inlet pressure Incorrect power supply Incorrect wiring Incorrect working conditions Thermal protection intervention Check Damaged pressure switch Replace High exhaust...

Страница 42: ...Chillers and Inverter Air Water heat pumps with axial fan 42...

Страница 43: ...43 Chillers and Inverter Air Water heat pumps with axial fan...

Страница 44: ...Fonderie Sime S p A Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it...

Отзывы: