Adjusting the burner at various installation altitudes
The appliance leaves the factory calibrated for operating at sea level.
(***)
Data measured with flue draught of 0 mbar
ALTITUDE
DUETTO HE EV
25
35
Nozzle
Pump pres-
sure *
(bar)
Diesel flow
rate **
(kg/h)
Air shutter
(notch)
Nozzle
Pump pres-
sure *
(bar)
Diesel flow
rate **
(kg/h)
Air shutter
(notch)
0
m.a.s.l. Danfoss 0,55
x 60° H
12
2,18
3.5
Danfoss 0,65
x 60° H
12
2,9
5,5
(*)
The pump pressure stabilises after roughly 5 minutes of operation.
(**)
Diesel flow rate value referred to a lower heating value (Hi) of 12,01 kWh/kg.
When the thermal unit is installed at altitudes up to maximum 1,300 m.a.s.l., due to the lower air density, the factory adjustments for
the burner must be modified as follows:
– keep the nozzle mounted in the factory
– do not vary the position of the combustion head
– gradually reduce the pump pressure to reduce the fuel flow rate
– adjust the air shutter by taking the following readings:
- CO
2
(%)
- CO (ppm)
- NOx (ppm)
- Bacharach index
- flue gas temperature.
a
WARNING
All operations must be carried out exclusively by the Sime Technical Support Service or by professionally qualified personnel,
according to the instructions appearing in this manual under the paragraph
Содержание 8103296
Страница 2: ...2...
Страница 6: ...6 IT...
Страница 12: ...12 IT...
Страница 26: ...26 IT...
Страница 47: ...47 IT...
Страница 48: ...48 EN...
Страница 52: ...52 EN...
Страница 58: ...58 EN...
Страница 72: ...72 EN...
Страница 93: ...93 EN...
Страница 97: ...97 EN IT...
Страница 98: ...98 EN IT...
Страница 99: ...99...
Страница 100: ...Fonderie Sime S p A Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 www sime it...