SGI ICE XA E-Cell Rack Assemblies
007-6399-002
53
Cooling Distribution Unit (CDU) Rack Specifications
The cooling distribution unit (CDU) is an interface between the building chilled water system and
the processor cold sinks in the E-rack assembly. It is designed to circulate and control chilled water
to the water manifolds that are in the E-rack with the compute blades. The CDU is rated for up to
305kW (1040.6 BTU/H) of cooling. The CDU consists of a rack-style cabinet that houses a heat
exchanger, circulating pump(s), control valve, receiver, controls, valves, and piping. The CDU
monitors room conditions and prevents coil condensation by maintaining the chilled water being
pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling water temperature, etc., are
automatic.
Table 4-4
SGI ICE XA Cooling Distribution Unit (CDU) Specifications
Characteristic
Specification
CDU height
74.2 in. (188.5 cm)
CDU width
23.6 in. (60 cm)
CDU depth
39.4 in. (100 cm)
Shipping height/width/depth
82 in. (208.3 cm) x 29.3 in. (74.5 cm) x 45.1 in. (114.3 cm)
CDU weight
727.5 lbs. (330 kg) dry | 846.5 lbs. (384 kg) water filled
CDU shipping weight
Approximately 1,068 lbs. (485 kg)
Voltage range
Nominal
Tolerance range
North America & Japan/International
480 VAC ___________/400 VAC
456-504 VAC _______/312-457 VAC
Frequency
Nominal
Tolerance range
North America/International
60 Hz / 50 Hz
47-63 Hz / 47-63
Phase required
3-phase
Power requirements (max)
4.67 kVA (4.3 kW)
Power cable
8 ft. (2.4 m) pluggable cords
Sound power
Approximately 55 dBA
Содержание ICE XA
Страница 1: ...SGI ICE XA System Hardware User Guide Document Number 007 6399 002 ...
Страница 4: ......
Страница 12: ......
Страница 25: ...Powering the System On and Off 007 6399 002 7 Figure 1 4 Three Phase PDU Example ...
Страница 32: ......
Страница 65: ...SGI ICE XA Series D Rack 42U 007 6399 002 47 Figure 4 1 D Rack Front Lock Example ...
Страница 66: ...48 007 6399 002 4 Rack Information Figure 4 2 Optional Water Chilled Door Panels on Rear of ICE XA D Rack ...
Страница 72: ...54 007 6399 002 4 Rack Information Figure 4 4 E Cell Rack Assembly Example CDU on Left ...
Страница 82: ......