The IntelliKnight

®

IP Communicators and an Ethernet connection simply replace the telephone lines as the

primary communications path to the central station. It connects to customer supplied network equipment with a

gateway to the Internet. The communicators provide supervised telephone line voltage to both panel DACT

ports. Upon network communication loss, telephone line voltage is dropped to the panel and panel reports

communication loss trouble. The communicators monitor the connectivity to both the primary and secondary

receiver at the central station. For more information about this panel and other Silent Knight products please call

800-328-0103.

IntelliKnight

®

Models 

SK-IP-2/SK-IP-2UD

IP Fire Alarm Communicators

INTELLIKNIGHT IP FIRE ALARM COMMUNICATOR

Description

The new IntelliKnight® SK-IP-2 and SK-IP-2UD are IP communi-

cators, UL listed for monitoring of Silent Knight fire alarm

panels.(See compatibility table) The SK-IP-2 has two supervised

inputs, and two additional outputs.The SK-IP-2UD version 6.0 adds

a modem daughter board (2UD) that supports upload/download

over the Internet or a customer's Intranet for IntelliKnight models

5820XL and 5808 FACP’s. These IP Communicators are UL 864

listed for signaling under Other Transmission Technologies and

comply with NFPA 72 requirements.  Refer to the IP Communicator

Series Installation Document PN 53109 for more information.
Both models connect to the primary and secondary communication

ports of the panel's DACT, converting the analog signals into digital

signals at the panel for transmission to a compatible Teldat

VisorALARM PLUS IP receiver at a central station. The panel

operates normally during an alarm, supervisory or trouble event

and sends contact-ID formatted analog information out of the

telephone ports to the IP Communicator. The IP Communicator

reformats the data into highly encrypted Ethernet UDP packets for

transmission to a compatible receiver at the central station. This

new listing only requires an IP connection. No backup analog

phone line is necessary.
Designed to work with compatible Contact ID DACT-equipped

addressable panels from Silent Knight, the IP Communicators

allow for faster and more economic digital alarm transmissions,

improving response times and decreasing costs found with

traditional analog systems. They offer value-added features such

as supervised line functionality, where a central station can detect

any off-line alarm panels within seconds. On the central station

side, a compatible VisorALARM® Plus IP receiver from the Teldat

Corporation allows seamless integration into existing conventional

central station architectures.

The benefit of an IP Communicator is that it is always on,

increasing the security and supervision of the central station

connection from once every 24 hours for a supervisory test signal

to once every 30 - 90 seconds.

The SK-IP-2UD allows a programmer to upload and download data

between the user's PC and either the IntelliKnight 5808 or 5820XL

addressable FACP. The panel and PC can be anywhere on the

world wide web or within a corporate intranet. 

The user’s computer runs a program called UDPORT.exe to

capture the modem signals from  or the newer PS-TOOLS panel

programming software. In UDPORT.exe the user enters the main

IP address of the 

VisorALARM receiver, the UDP port to use, username,

and password Instead of using the PC’s modem, this

process communicates between the SK-IP-2UD’s

modem at the panel and the panel’s own modem.

While speed is still limited to the baud rate of the

panel's modem, panel communications are now 100%

digital over IP from the remote program PC all the way

to the remote panel installation. This eliminates any

dropouts in modem communications caused by noise

or other factors. If an alarm should occur during upload

or download, the panel is able to interrupt modem

communications immediately and transmit the alarm to

the central station.
Each SK-IP-2UD is registered in the VisorALARM

Receiver with a unique serial number. A subscriber

number must be entered into the subscriber number

database field for each SK-IP-2UD. This same number

is entered into the subscriber telephone number field

(panel to call) in PK-PLUS or PS-TOOLS as if calling

the panel on a telephone. If these numbers match, and

the master username and password are correct, full

duplex communication is permitted to the panel.

NOTE:

UL 864 Ninth Edition prohibits downloading 

to

a panel without entering a local panel password.

Uploading is permitted at any time without

entering a password.

IP Communicator

Содержание INTELLIKNIGHT SK-IP-2

Страница 1: ...or faster and more economic digital alarm transmissions improving response times and decreasing costs found with traditional analog systems They offer value added features such as supervised line functionality where a central station can detect any off line alarm panels within seconds On the central station side a compatible VisorALARM Plus IP receiver from the Teldat Corporation allows seamless i...

Страница 2: ...ftware shipped with IP Communicator or downloaded from www silentknight com The IP Communicator can be pre programmed The programmer enters all central station information and an auto registration password This is saved to the unit s flash memory When the IP Communicator is installed at the site and connected to the Internet Intranet it registers itself with the central station receiver This elimi...

Страница 3: ... the central station Panel account ID number CID Installer password provided by the monitoring station managing the IP receiver Separate username and password supplied by central station for upload download operation Note this is different than installation password Mounting Methods 1 The IP Communicator is included with the SK IP 2 2UD and can be mounted inside the small IPENC enclosure IPENC is ...

Страница 4: ... IPSPLT Y adaptor option to allow connection of both panel dialer outputs to one cable input to IPDACT 2UD ALMSC 119 Required serial programming cable sold separately HP300ULX Honeywell Power Products UL 1481 listed auxiliary power supply Enclosure must be close nipple to a panel no further than 6 15cm via conduit Requires IPBRKT purchased separately INTELLIKNIGHT IP FIRE ALARM COMMUNICATOR PN 350...

Отзывы: