System Operation
151430
10-15
10.7 Releasing Operations
This control panel supports two types of releasing, Double Interlock Zone, and Single
Interlock Zone. The Double Interlock Zone operation requires an interlock switch input in the
system, and the Single Interlock does not. An interlock switch is typically a dry-contact
pressure switch.
When a Single or Double Interlock Zone releasing is selected the system is will automatically
default the following system parameters:
Note: The defaults created can be modified through programming if desired.
•
Output Group 2 is created. Output Group 2 will be defaulted as an “Alarm” output group
for all releasing zones. NAC [98:001] is assigned to Output Group 2.
•
Output Group 3 is created. Output Group 3 will be defaulted as an “Pre-Alert” output
group for all releasing zones. NAC [98:002] is assigned to Output Group 3.
•
Output Group 4 is created. Output Group 4 will be defaulted as a “Release” output group
for all releasing zones. NAC circuit [98:003] is assigned to Output Group 4.
Note: The installer must define which input points will be used for detectors, manual release switches, or inter-
lock/pressure switches
Table 10-2 Approved Releasing Solenoids.
Figure 10-4 Wiring Configuration for Solenoid
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Model 7641
Must be Mounted
at the Solenoid
Releasing solenoid
Use 24 VDC, UL listed model in table 10-2
1 solenoid per circuit
Содержание IFP-2000
Страница 2: ......
Страница 12: ...IFP 2000 Installation Manual viii...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430...
Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430...
Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description...
Страница 230: ...IFP 2000 Installation Manual A 14...
Страница 232: ...IFP 2000 Installation Manual B 2 151430...
Страница 236: ......
Страница 237: ......