IFP-2000 Installation Manual
10-14
151430
10.6 Multi-Site Annunciator and Multi-Site user
Access
Multi-site displays are unique as they can display the status and event history of all sites they
are assigned to. These displays can be especially useful in guard shacks or security centers. A
multi-site display is indicated by the words “Multi-Site Display” at the top of the idle screen.
1. The ACK, DRILL, RESET and F-Macro keys are disabled until a multi-site user password
has been entered and a specific site has been selected
2. Multi-site silencing rules:
•
If any of the assigned sites are silenced, the Silenced LED will be lit.
•
Silence key will only silence the sound from the multi-site annunciator on which the
silence key was pressed. This is called being Locally Silenced. If Locally Silenced is
enabled on a multi-site annunciator, it will be indicated by a blinking Silenced LED.
•
If any new troubles, supervisory, pre-alarms, or alarms are triggered in any assigned
sites, Locally Silenced will become disabled.
•
If a multi-site annunciator is locally silenced for 24 hours, the locally silenced feature
will be disabled.
3. The IFP-2000 menu system is disabled on a multi-site annunciator. Pressing the Right or
Enter keys will bring you straight into event history for assigned sites. To get into the
menu system, a multi-site user password must be entered and then a site selected from the
site selection menu. Once this is done you will have access to the idle screen of that site
and the annunciator will temporarily act like a single site annunciator.
4. A multi-site annunciator will sound the highest priority tone from the sites it is assigned
to.
Note: A multi-site display is created in Module programming in the edit properties menu for an RA-2000. See
section 9.2.1.
Содержание IFP-2000
Страница 2: ......
Страница 12: ...IFP 2000 Installation Manual viii...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430...
Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430...
Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description...
Страница 230: ...IFP 2000 Installation Manual A 14...
Страница 232: ...IFP 2000 Installation Manual B 2 151430...
Страница 236: ......
Страница 237: ......