Programming
151430
9-1
Section 9
Programming
This section of the manual describes how to manually program the control panel from the
built-in annunciator. Each subsection discusses these menu options in detail. All options
described in this section can be performed using the Silent Knight Software Suite (SKSS-2).
9.1
UL 864 Programming Requirements
Important!
Before any customized programming is done, JumpStart AutoProgramming should be
run first. After JumpStart is run, thoroughly test the system. The reason the system
should be tested after JumpStart AutoProgramming is because Jumpstart
AutoProgramming automatically programs the system, searching for and configuring
all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the
hardware is properly installed, custom programming can be performed. Refer to
Section 8.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND
OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In
order for the product to comply with the requirements in the Standard for Control Units and
Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be
limited to specific values or not used at all as indicated below.
Programming Option
Menu Item
Permitted in
UL 864 (Y/N)
Possible Settings
Settings Permitted
in UL 864
Misc Options 1
Low AC Report Delay
Yes
0–30 hours
1–3
Switch
Water Flow
Yes
latching and non latching
latching
Phone Line
Enable Gnd Start
No
Yes & No
No
Misc. Opt 3
Alarm Verification
Yes
1-250 seconds
60-250 seconds
Содержание IFP-2000
Страница 2: ......
Страница 12: ...IFP 2000 Installation Manual viii...
Страница 22: ...IFP 2000 Installation Manual 1 10 151430...
Страница 26: ...IFP 2000 Installation Manual 2 4 151430...
Страница 31: ...Before You Begin Installing 151430 3 5 Figure 3 1 Wire Routing Example...
Страница 100: ...IFP 2000 Installation Manual 5 14 151430...
Страница 124: ...IFP 2000 Installation Manual 8 8 151430 Figure 8 4 Example of Zone Events Mapped to output Groups and Patterns...
Страница 125: ...Programming Overview 151430 8 9 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns on a Single Panel...
Страница 194: ...IFP 2000 Installation Manual 10 20 151430...
Страница 210: ...IFP 2000 Installation Manual 12 8 151430...
Страница 215: ...Installation Records 151430 13 5 Module Addr Zone Group Description Module Addr Zone Group Description...
Страница 230: ...IFP 2000 Installation Manual A 14...
Страница 232: ...IFP 2000 Installation Manual B 2 151430...
Страница 236: ......
Страница 237: ......