Instruction Manual FireGuard 2
Servicing
80
13542E/4
Pos : 160 /Wart ung/Fir eG uar d 2/Tit el N ac hkali brierung.. . @ 4 \ mod_1447922235033_20. doc x @ 22529 @ 2 @ 1
9.4
Recalibrating the FireGuard 2
Pos : 161 /Wart ung/Fir eG uar d 2/ Allgemei nes z ur Nachkalibri erung FireG uard 2 @ 4\ mod_1437552830757_20. doc x @ 21299 @ 3 @ 1
9.4.1
General information on recalibrating the FireGuard 2
Recalibrating the photometer can result in deviations from the previous measuring value as
the instrument is newly reset to a reference value (checking unit). The instrument should be
cleaned before recalibration according to Section 9.2.
Recalibration can be triggered via the SICON-C portable control unit, or automatically by
plugging in the checking unit. The automatic triggering of a recalibration can be activat-
ed under
Recalibration\General\Auto start recal.
.
The nominal values on two checking units can be saved in the FireGuard 2. The checking
units are identified via a serial number.
The checking unit currently in use must be defined in the
Recalibration\C1\Cont. ac-
tive
menu. Checking unit 1 is set as standard.
Pos : 162 /Wart ung/Fir eG uar d 2/ Eins tell en der ver wendet en Kontr olleinheit-Nummer FireGuard 2_Vi sG uar d @ 4\ mod_1437553537940_20. doc x @ 21306 @ 3 @ 1
9.4.2
Setting checking unit number in use
WORKSTEP
ADDITIONAL INFO / IMAGES
1.
Switch to service mode as described in Section
7.11.
2.
Select the checking unit currently in use in the
Recalibration \ C1 \ Cont. active
menu.
Pos : 163 /---Seit enumbruc h--- @ 0\ mod_1341482862121_0. doc x @ 4073 @ @ 1
Pos : 164 /Wart ung/Fir eG uar d 2/M anueller Abgleic h Fir e G uard 2 mi t SICON C @ 4 \ mod_1437469878930_20. doc x @ 21289 @ 3 @ 1
9.4.3
Manual adjustment with a SICON-C
The following procedure describes how manual adjustment is made with a SICON-C:
WORKSTEP
ADDITIONAL INFO / IMAGES
1.
Plug in the SICON-C on the SIPORT 2 connec-
tion box.
2.
Remove the contamination protection by re-
moving both screws (circles) on the photome-
ter.
The photometer can be left in the
measuring position when installed in walls
and ceilings. When installed in suspended
ceilings, the instrument has to be removed
from the measuring position according to
Section 4.3.
3.
Switch the photometer to service mode as de-
scribed in Section 7.11.
4.
Check the serial number of the checking unit
against the number of the instrument. These
must match.