Settings
Instruction Manual FireGuard 2
13542E/4
67
Pos : 144 /Bedi enung/Modbus RTU Par ameter einst ellen @ 4 \ mod_1442069732625_20. doc x @ 21630 @ 2 @ 1
8.7
Setting the Modbus RTU parameters
This setting only has to be carried out if the optional Modbus module is used.
MANIPULATION
ADDITIONAL INFO / IMAGES
1.
Press the
Menu
button.
2.
Enter the access code and confirm with
OK
.
Factory setting is
0
.
3.
Press the
Digi. interf.
button.
4.
Press the
Modbus
button.
5.
Enter the desired number under
Slave no.
.
Values between 1 and 240 are pos-
sible.
6.
Select the
Baudrate
menu.
Values between 4800 and 230400
baud are possible.
7.
Select the
Parity
menu.
The settings
None
,
Even
and
Odd
are possible.
8.
Select the
Stopbit
menu.
1 or 2 Stopbit are possible.
9.
Press the
Meas
button. The parameters are
activated.
The instrument is in measuring
mode again.