Safety Instructions

  1.  Prior to installation or removal:

•  Depressurize and vent system
•  Drain below sensor level 

  2.  Confi rm chemical compatibility before use.
  3.  Do not exceed maximum temperature/pressure specifi cations.
  4.  Wear safety goggles or faceshield during installation/service.
  5.  Do not alter product construction.
  6.  Dispose of properly; DO NOT INCINERATE!

Signet 2250 Hydrostatic Level Sensor

1. Description

2. Specifi cations

The Signet 2250 Hydrostatic Level Sensor uses a gauge pressure sensor to calculate the level of fl uid in a tank. Gauge pressure 
sensors measure the difference in pressure between the process on one side of a diaphragm and the atmospheric pressure on the 

opposite side of the diaphragm. A tiny capillary tube running from inside the sensor body and up the length of 

the cable provides the reference to atmospheric pressure.

Hydrostatic level measurement can be a simple and practical solution to those applications where the fl uid 
temperature is stable and constant.

IMPORTANT!  This method of level measurement is not recommended if the fl uid is subject to 
temperature variations or any other variable that causes the density of the fl uid to change. 

The 2250 Hydrostatic Level Sensor has excellent chemical compatibility.  The wetted materials are PVDF, 
Ceramic and FPM.

Several different hardware mounting kits are available to accommodate every installation requirement.

3-2250.090  

 

Rev. A 12/06 

 

English

*3-2250.090*

English

Dimensions

½ in. (ANSI) or
25 mm (ISO)
Solvent Socket,
PVC-U

34 mm

(1.32 in)

115 mm
(4.55 in)

53 mm
(2.09 in)

General

Compatibility: 

Signet 8250-2 and -3 Level Transmitters

  

Signet 

8900 

Multi-Parameter 

Controller

Standards and Approvals:
• CE
• 

Manufactured under ISO 9001:2000 for Quality and

 

ISO 14001:2004 for Environmental Management

Wetted Material
• Sensor 

housing: 

PVDF

• Union 

nut/bushing: 

PVC-U

• Diaphragm: 

 

 

 

Ceramic

• 

Diaphragm seal:   

FPM (optional EPDM)

Cable type: 

 

22 AWG, 3 cocapillary tube

Cable length: 

 

10 m (32.8 ft.) supplied

 

 

 

max. extension 120 m (400 ft.)

Operating Temperature: 

15˚C to 85˚C (5˚F to 185˚F)

Storage Temperature: 

-20˚C to 100˚C (-4˚F to 212˚F)

Operating Pressure: 

-XU:  0 to 0.7 bar (0 to 10 psig)

 

 

 

-XL:  0 to 3.4 bar (0 to 50 psig)

Electrical

Digital (S

3

L) Output:

• 

Format: 

 

Serial ASCII, TTL level 9600 bps.

• 

Accuracy: 

 

±1% of full scale (±0.001 psi)

• 

 Power: 

 

5 VDC nominal, 1.5 mA max. current

 

 

 

(5 VDC min, 6.5 VDC max)

• 

Reverse polarity and short circuit protected

4 to 20 mA Output:
• Factory 

span:

•  -XU: 0 to 0.7 bar (0-10 psig) = 0-7 m (23 ft.) of water
•  -XL: 0 to 3.4 bar (0-50 psig)  = 0-34 m (115.5 ft.) of water

• Accuracy:  

±32 

µA

• Resolution: 

 

<5 

µA

• Response 

Time: 

 

<100ms

• 

Loop Power Required:  12 to 24 VDC nominal, 22.1 mA max

 

 

 

(10.8 VDC min. to 26.4 VDC max.)

• 

Max. Loop Impedance:

  

 

100Ω 

12V

  

 

325Ω 

18V

  

 

600Ω 

24V

Содержание 2250

Страница 1: ...lity The wetted materials are PVDF Ceramic and FPM Several different hardware mounting kits are available to accommodate every installation requirement 3 2250 090 Rev A 12 06 English 3 2250 090 English Dimensions in ANSI or 25 mm ISO Solvent Socket PVC U 34 mm 1 32 in 115 mm 4 55 in 53 mm 2 09 in General Compatibility Signet 8250 2 and 3 Level Transmitters Signet 8900 Multi Parameter Controller St...

Страница 2: ...ENSORS WITH CARE The 2250 can be assembled as a blind 4 20 mA signal connected by cable to a PLC Chart recorder or other 4 20 mA device This type of installation requires no additional hardware The user must provide the in conduit to protect the cable from damage The 2250 cable is not suitable for direct submersion Multi Parameter Controller C1 2 50 µS cm L2 58 43 M Relay 1 Relay 2 ENTER 3 2250 1x...

Страница 3: ...er supplied 3 2250 xx 3 8050 1 PLC PLC 4 20 mA Out 4 20 mA Out 4 20 mA or Digital S3L signal out Clamped to Tank support 4 20 mA or Digital S3L signal out Mounted through Tank Cover 3 8250 2 3 8250 3 3 8900 3 8250 2 3 8250 3 3 8900 Signet Level Transmitter Signet Level Transmitter Level 10 00 ft Relay 1 Relay 2 ENTER Signet Level Transmitter Signet Level Transmitter Level 10 00 ft Relay 1 Relay 2 ...

Страница 4: ...es at the terminal block inside the conduit base CAUTION The capillary tube that runs the length of the sensor cable must remain open to the atmosphere Do not allow it to be crimped or blocked PLC 4 20 mA Out Signet Level Transmitter Digital S3L OR Multi Parameter Controller C1 2 50 µS cm F2 58 43 GPM Relay 1 Relay 2 ENTER Signet Level Transmitter Level 10 00 ft Relay 1 Relay 2 ENTER Integral syst...

Страница 5: ...Black Freq Input 2 Red S L Red GND White Shield 5VDC Black S L Red GND White Shield 3 3 Analog Output 1 Analog Output 2 if applicable if applicable Frequency Input 1 Frequency Input 2 OR S3L Input 2 S3L Input 1 Black Red White Shield Multi Parameter Controller Lvl1 4 20 m Lvl2 8 53 m Relay 1 Relay 2 ENTER Black Red Shield Gnd I O V 13 12 11 White Signet Level Transmitter Level 10 00 ft Relay 1 Rel...

Страница 6: ...mA Loop Monitor Chart Recorder Datalogger Power Supply DC 12 24 V Black Loop White Loop Cable shield Red no connection Optional Earth ground 3 2250 21U 159 001 248 4 20 mA 0 to 0 7 bar 0 10 psig 0 to 7 m 0 to 23 09 ft 3 2250 21L 159 001 247 4 20 mA 0 to 3 4 bar 0 50 psig 0 to 34 m 0 to 115 5 ft 3 2250 22U 159 001 251 4 20 mA 0 to 0 7 bar 0 10 psig 0 to 7 m 0 to 23 09 ft 3 2250 22L 159 001 252 4 20...

Страница 7: ...Fill tank to the level represented by 4 mA 4 mA 20 mA Programmable Logic Controller 4 20 mA loop monitor Chart Recorder Datalogger Power Supply DC 12 24 V 15s Black Loop White Loop Red no connection Black Loop White Loop Red no connection The 4 to 20 mA span can be set to accommodate any application within the operating range of the sensor The respanning procedure requires that the sensor be subje...

Страница 8: ... U S 800 854 4090 3 2250 090 Rev A 12 06 English George Fischer Signet Inc 2006 Printed in U S A on Recycled Paper Sensor Part Number 3 2250 Hydrostatic Level Sensor Sensor Output 1 Digital S3 L 10 m 32 8 ft 2 Current 4 to 20 mA 10m 32 8 ft Threaded Connection 1 in union connector 2 in NPT threads Operating Pressure Range U 0 0 7 bar 0 10 psi L 0 3 4 bar 0 50 psi PVC U Union Connection in socket 1...