Figure 3-2. The trigger input and output lines are isolated by an optical isolators.
TrigIn -
This is the trigger input signal. It requires TTL or CMOS level (at least 2.5V) to activate the trigger input.
A series 1k removes the need to add external resistor and allows direct connection to a TTL or CMOS logic source.
It is referenced to the
TrigComm
line.
TrigOut -
This is the trigger output signal. It is an open collector signal with 1k resistor in series. It will drive a
CMOS or TTL line provided it is connected to an appropriate positive supply (from 3V to 10V). It is referenced to
the
TRIG_ comm
line.
+5V -
This is a 5V supply line. It is designed to support the optional active Isothermal Block. It may also be used to
power the
TrigOut
signal. When using it to power
TrigOut
, it is recommended that a 10k be connected from
TrigOut
to it as in Figure 3-3. This supply may vary between 4.7V to 5.7V, and its usage should be limited to no
more than 10mA. This supply is isolated from the rest of the signals in the DB-78 connector. This signal is
referenced to the
PowerComm
line.
PowerComm -
This is the return line for the
+5V
supply. Since
TrigComm
and
PowerComm
are isolated from
each other, they must be connected as in Figure 3-3 if the
+5V
is used to power
TrigComm
. This supply return is
isolated from the rest of the signals in the DB-78 connector.
Figure 3-3. Trigger out may use the +5V supply provided for generating logic output.
3.5 Starting the Control Panel
After installing the software, you can verify the installation and gain familiarity with the Scanner by exercising its
measurement functions using the Windows based Control Panel. To run the control panel, double click the
‘SMX4032.EXE’ icon. If you do not hear the relays click, you may have an installation error.
The Control Panel is operated with a mouse. All functions are accessed using the left mouse button.
Note: The SMX4000 front panel powers up in Disabled mode, with all relays open.
3.6 Using the Control Panel
15
Signametrics