![SIGNAL FIRE GWS-CBBL Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/signal-fire/gws-cbbl/gws-cbbl_interface-manual_1268237026.webp)
Rev 4.9
SignalFire Telemetry
26
Register
Address
Register
Number
Description
R/W
0151
00152
Digital Output Module 2 Relay 9
R/W
0152
00153
Digital Output Module 2 Relay 10
R/W
0153
00154
Digital Output Module 2 Relay 11
R/W
0154
00155
Digital Output Module 2 Relay 12
R/W
7100
07101
RSD Force Shutdown
R/W
Holding Registers
Read holding registers with Modbus opcode 0x03 (Read Holding Registers) or 0x04 (Read Input Registers).
Write holding registers with Modbus opcode 0x06 (Write Single Register) or 0x16 (Write Multiple Registers).
Register
Address
Register
Number
Description
R/W
1000
41001
System Reset: Resets the gateway and radio
R/W
1001
41002
Radio Reset: Resets the radio leaving the gateway on
R/W
1002
41003
Counter Reset: Resets all GW status counters to zero (See Read Only Registers 2026-
2031)
R/W
1003
41004
Radio Network
R
1004
41005
Radio Network Group
R
1005
41006
Radio Corporate ID
R
1101
41102
Analog/Relay Output Module 1 Relay 1
R/W
1102
41103
Analog/Relay Output Module 1 Relay 2
R/W
1103
41104
Analog/Relay Output Module 2 Relay 1
R/W
1104
41105
Analog/Relay Output Module 2 Relay 2
R/W
1119
41120
DIN GW Digital Output 1 Pulse (Seconds to pulse output on)
W
1120
41121
DIN GW Digital Output 2 Pulse (Seconds to pulse output on)
W
1121
41122
Analog/Relay Output Module 1 Relay 1 Pulse (Seconds to pulse relay on)
W
1122
41123
Analog/Relay Output Module 1 Relay 2 Pulse (Seconds to pulse relay on)
W
1123
41124
Analog/Relay Output Module 2 Relay 1 Pulse (Seconds to pulse relay on)
W
1124
41125
Analog/Relay Output Module 2 Relay 2 Pulse (Seconds to pulse relay on)
W
1131
41132
Digital Output Module 1 Relay 1
R/W
1132
41133
Digital Output Module 1 Relay 2
R/W
1133
41134
Digital Output Module 1 Relay 3
R/W
1134
41135
Digital Output Module 1 Relay 4
R/W
1135
41136
Digital Output Module 1 Relay 5
R/W