BUILD-IN TOUCH TERMINAL
TAE 2144
7 Assembly/Installation
7.1 Check Contents of Delivery
Ensure that the contents of the delivery are complete and intact. See chapter 1.3 Contents
of Delivery.
INFORMATION
On receipt and before initial use, check the device for damage. If the
device is damaged, contact our customer service and do not install the
device in your system.
Damaged components can disrupt or damage the system.
7.2 Installation
The device’s power loss can reach up to 30 Watts. To ensure the necessary air circulation
for cooling, the mounting instructions must be followed!
7.3 Mounting Instructions
The following instructions must be followed when installing the terminal:
l
For installation with the screw terminals provided, it is recommended that the
installation panel have a material strength of at least 1 mm and a maximum of 2
mm. The screw-in brackets can be tightened with a maximum torque of 0.2 Nm. For
this purpose, a 3x 0.5 flat-tip screw driver is required.
l
To avoid damage to the aluminum frame, it is important to ensure that during
installation, the contact surface is clean (free of debris, uneven areas). Unevenness
can lead to stress on the glass/aluminum frame or contamination from dust and
water.
l
To minimize the probability of damage to the PIM or plug contacts of the TP during
installation, we recommend installing the TP after the PIM has been mounted.
To dissipate waste heat from the terminal, the clearance between the back of the terminal
(heat sink) and the back wall of the control cabinet should be at least 80 mm.