S-DIAS SAFETY DIGITAL MIXED MODULE
SDM 081
07.02.2022
Page 15
3.3
Input Circuit
3.4
Output Specifications
All safety outputs are short-circuit protected and specified in accordance with
EN 61131-2. The outputs are compatible with input of Types 1, 2 and 3.
Number
2
Rated output voltage
+24 V DC
Output voltage range
m18 V
m30 V
Maximum output current
2 A
Maximum total current
(2 outputs)
4 A
up to a max. environmental temperature of 55 °C
Brake voltage with switching-off
inductive loads
typically 0.85 V
Maximum switch-off energy of the
outputs (inductive load)
maximum 0.4 Joule per channel
Turn-on delay
< 200 µs
Turn-off delay
< 1 ms
Miscellaneous
Short-circuit proof
Cutoff test pulse width (t
1
)
minimum 0.1 ms
maximum 1.5 ms
Cutoff test pulse interval bet. FET
Test and HSS Test (t
2
)
minimum 112 ms
maximum 6450 ms
Cutoff test pulse interval (t
3
)
60 s