background image

 

S-DIAS SAFETY CPU MODULE 

SCP 011 

 

28.02.2020 

Page 23 

6.1.2 

Command Selection Sequence 

After  the  Start  sequence,  the  desired  command  is  selected.  This  selection  is  made  with 
button presses in the following time intervals: Minimum press duration is 200 ms, maximum 
is approximately 3 seconds; the minimum pause between individual button presses is 200 
ms, the maximum is 10 seconds. After each correct button press (incl. The minimum pause 
of approx. 200 ms), the selected command is shown with LEDs C1, C2 and C3. If an invalid 
command  is  selected  (see  "valid  commands"),  the  Error  sequence  is  initiated;  as  with  not 
correctly observing the time intervals. LED B lights continuously during this sequence. 

 
 

6.1.3 

End Sequence 

This sequence is used to confirm the selected command. Here, the button is pressed until 
LED starts to blink (approx. 3 seconds, blinks in a slow interval). The number of light pulses 
in LED B depends on the previously selected command (see "valid commands").  

After  the  LED  turns  off,  the  button  must  be  released.  After  the  minimum  pause  of 
approximately  200  ms,  in  which  the  button  must  not  be  pressed,  the  service  mode  is 
imitated and the command is executed. If the button pressed for longer than approximately 
3  seconds,  the  selected  command  is  not  accepted  and  the  Error  sequence  is  displayed. 
The same applies when the button is released too soon or the minimum pause of 200 ms is 
not observed. After executing the command, the corresponding mode is initiated depending 
on the command (see "Valid Commands"). 

If  executing  the  command  leads  to  an  error  (e.g.  because  SET_VERIFIED  should  be 
executed  although  no  valid  configuration  data  is  available  in  the  Safety  CPU),  the  Error 
sequence is initiated.  

 

Содержание SCP 011

Страница 1: ...SCP 011 S DIAS Safety CPU Module Date of creation 18 12 2013 Version date 28 02 2020 Article number 20 890 011 E...

Страница 2: ...rt of this work may be reproduced edited using an electronic system duplicated or distributed in any form print photocopy microfilm or in any other process without the express permission We reserve th...

Страница 3: ...e PL e EN ISO 13849 1 2 The safety related SCP 011 is ideal for use in systems with optional modules and interface variables according to Safety System Handbook see homepage1 The SCP 011 module alone...

Страница 4: ...Safety Standards 10 2 2 EU Conformity Declaration 10 2 3 Safety Relevant Parameters 10 2 4 Compatibility 11 3 Technical Data 12 3 1 Performance Data 12 3 2 Electrical Requirements 12 3 2 1 Module Supp...

Страница 5: ...Module Statuses and Commands 25 6 4 Handling the microSD Card 27 6 5 Configuring a Safety CPU with the SD Card 28 7 Error Response 30 7 1 Restart Errors 30 7 2 Configuration Distribution Error 31 7 3...

Страница 6: ...DANGER Identifies an immediate danger with high risk which can lead to immediate death or serious injury if not avoided Indique un danger direct haut risque d un d c s imm diat ou des blessures grave...

Страница 7: ...vertissement d une surface chaude Danger for ESD sensitive components Les signes de danger pour les composants sensibles aux d charges lectrostatiques This symbol identifies important or additional in...

Страница 8: ...tions importantes Distribuez la documentation technique aux secteurs de la vente et ou de la location du produit Acceptance of the Safety Guidelines Before handling the product belonging to this docum...

Страница 9: ...e and decommissioning of control and automation technology products in general as well as safety related products especially can only be performed by qualified personnel Qualified personnel in this co...

Страница 10: ...e outside of the technical data described in this handbook Utilisation pr vue Les modules de s curit sont con us pour une utilisation dans les applications sollicitant un niveau de s curit et r ponden...

Страница 11: ...y modules The documentation is complete and in readable condition and available at the site of operation Obligation de diligence L utilisateur doit s assurer que les modules de s curit ne sont utilis...

Страница 12: ...the Directive 95 16 EC machine guideline 2014 30 EU Electromagnetic Compatibility EMC guideline 2011 65 EU Restricted use of certain hazardous substances in electrical and electronic equipment RoHS G...

Страница 13: ...DINT are transferred and further processed an SCP011 with Firmware version V344 or higher MUST be used HW version 1 60 SAFEDINT variables are transferred when for two or more Safety CPU s in a project...

Страница 14: ...typically 24 V DC UL Class 2 or LVLC 1 Current internal consumption typically 90 mA internal consumption maximum 1 4 A 2 3 Current consumption from the S DIAS bus 5 V 24 V with missing 24 V connection...

Страница 15: ...usible doit tre certifi par un NRTL National Recognized Testing Laboratory par exemple UL 2 dependent on the number of connected modules on the S DIAS Safety bus 3 For loading the internal capacitors...

Страница 16: ...DIAS system blue moduls the voltage increase of the 24 V supply of the SCP 011 must not happen later than 100 msec after the voltage supply oft he S DIAS supply moduls otherwise it can happen that th...

Страница 17: ...S DIAS SAFETY CPU MODULE SCP 011 28 02 2020 Page 15...

Страница 18: ...al temperature by 0 5 C per 100 m Operating conditions Pollution degree 2 EMC resistance in accordance with 61000 6 7 2015 Generic standards Immunity requirements for equipment intended to perform fun...

Страница 19: ...S DIAS SAFETY CPU MODULE SCP 011 28 02 2020 Page 17 4 Mechanical Dimensions...

Страница 20: ...pin 4 are internally bridged To supply the module only one connection to a 24 V pin pin 1 or pin 2 and a GND pin pin 3 or pin 4 is required The bridged connections may be used for further looping of...

Страница 21: ...s in error mode Slow blinking frequency the maximum age has been exceeded for a removed input can be read with the SafetyDesigner Fast blinking frequency serious error communication with the module is...

Страница 22: ...Connections Stripping length Sleeve length 10 mm Plug in direction parallel to conductor axis or to PCB Conductor cross section rigid 0 2 1 5 mm2 Conductor cross section flexible 0 2 1 5 mm2 Conducto...

Страница 23: ...CP 011 28 02 2020 Page 21 5 3 Label Field Manufacturer Weidm ller Type MF 10 5 CABUR MC NE WS Weidm ller article number 1854510000 Compatible printer Weidm ller Type Printjet Advanced 230V Weidm ller...

Страница 24: ...nd End sequence and the sequence for selecting a command see the following diagram Buttons LED B LED C1 C3 6 1 Explanation of the Individual Sequences 6 1 1 Start Sequence The button must be pushed un...

Страница 25: ...elected command Here the button is pressed until LED starts to blink approx 3 seconds blinks in a slow interval The number of light pulses in LED B depends on the previously selected command see valid...

Страница 26: ...asts for at least 3 seconds If the button is still pressed after 3 seconds LED B will continue to blink until the button is released and a minimum pause of approximately 200 ms has elapsed The Start s...

Страница 27: ...R_CFG 2 X X SET_VERIFIED 3 X X X 6 3 Overview of Module Statuses and Commands The following tables show a sample of the statuses in which the system can be found the commands that can be active during...

Страница 28: ...ation in the Safety CPU is deleted After executing the command the Safety CPU is now in service mode Service mode SET_VERIFIED The configuration status is set to verified Operational mode A SW RESET i...

Страница 29: ...ed on an SD card The stored Safety project can then be loaded into an additional SCP Safety CPU providing that the module s Flash memory is empty cleared If the configuration on the SD card is differe...

Страница 30: ...ystem is restarted the configuration is loaded from the SD card into the Flash of the Safety CPU This is only possible if a valid configuration is stored on the SD card If the SD card has an incorrect...

Страница 31: ...12 630 101 Uniquement les cartes microSD supportant au moins la version 2 0 de la SDA Sp cification de la couche physique SDA SD Card Association peuvent tre utilis es Il est recommand d utiliser uniq...

Страница 32: ...in the Safety System Handbook as well For an exact error analysis the SafetyDesigner must be used 7 1 Restart Errors The following diagram shows the response of the Safety CPU module during restart Id...

Страница 33: ...th LEDs light simultaneously c If for whatever reason the distribution of the configuration is still not successful the Safety CPU switches to the Error Mode and the E LED lights d When the Safety CPU...

Страница 34: ...etested using the SafetyDesigner 7 4 Troubleshooting with the SafetyDesigner Connect the SafetyDesigner Debug the system using the SafetyDesigner 7 5 Correcting a Wiring Error When a wiring error is d...

Страница 35: ...ring circuits Protective circuits for all relays RC networks or free wheeling diodes Correct wiring to ground The ground bus should be connected to the control cabinet when possible Si possible la ter...

Страница 36: ...all of the control cabinet The individual S DIAS modules are mounted on the DIN rail as a block and secured with latches The modules must be mounted horizontally module label up with sufficient cleara...

Страница 37: ...S DIAS SAFETY CPU MODULE SCP 011 28 02 2020 Page 35 Recommended minimum distances of the S DIAS modules to the surrounding components or control cabinet wall a b c distances in mm inches...

Страница 38: ...d 10 2 Cycle Times equal to or higher than 1 ms in ms 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 x x x x x x x x x x x x x x x x x supported 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 x x x x x x x x...

Страница 39: ...30 01 2015 27 9 Wiring Guidelines Added note concerning connecting the S DIAS module while voltage is applied 26 03 2015 16 5 2 Applicable Connectors Added connections 07 05 2015 New writing EN ISO 1...

Страница 40: ...added 02 04 2019 10 16 all 2 3 Safety Relevant Parameters 3 4 Environmental Conditions Correction of the safety relevant parameters Corrections environmental conditions Corrections due to CE 01 10 20...

Отзывы: