DIAS-DRIVE 210-23
Page 28
30.03.2021
2.2.6
External Fuse
The AC and 24V fuse are designed according to the customer requirements for the circuit.
Signal
Fuses, inertia
AC voltage supply (L1-L3)
The size of the fuse depends on the average power consump-
tion of the connected amplifier. Max. 20 A with 4 mm
2
(12
AWG) (FRS-25) wires
24 V DC input (24 V, 24 V-
BR)
16 A inertia with 2.5 mm² (14 AWG) for the control
External brake resistance
10 A time delay, 1200V (e.g. SIBA 10 022 01, 3-pin, D-Fuse-
Link) or FRS-10
UL Requirement:
Suitable for use on a circuit capable of delivering not more than 5000 rms symmetrical
amperes, 528 volts maximum when protected by RK5 class fuses rated 20A.
Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the Manufacturer Instructions, Na-
tional Electrical Code and any additional local codes.