2 Installation
2.1 Important Guidelines
•
When using a ground fault interrupter in the circuit, a type B FI-switch
is required. If an FI switch of type "A" is used, A DC ground fault could
cause it to malfunction. High-frequency leakage currents occur, which
must be taken into consideration when selecting the FI (e.g. Schrack
ID-B 4/XX/XX-B). Trigger diagram:
•
The servo amplifier and motor must be grounded according to the
guidelines. Uncoated mounting plates must be used in the control
cabinet.
•
The DIAS Drive must be connected to the ground terminal over a wire
with a cross section of at least 10 mm² (8 AWG).
•
The main power supply for the DIAS Drive requires a fixed connection.
If the servo amplifier is mounted on a moving part over a connector
terminal, the ground wire must have a cross section of at least 10 mm²
(8 AWG) to avoid high leakage current (>3.5 mA).
•
Before installation, the servo amplifier must be mechanically tested. If
damage resulting from transportation is determined, for example, the
amplifier cannot be used. Electronic components cannot be physically
handled.
•
The rated voltage and current specifications of the servo amplifier and
motor must match. The electrical connection must correspond to the
schematicon page 35.
Содержание DIAS-DRIVE 210-23
Страница 8: ...DIAS DRIVE 210 23 Page 8 30 03 2021 1 4 Servo Amplifier Components ...
Страница 12: ...DIAS DRIVE 210 23 Page 12 30 03 2021 1 8 Block Diagram ...
Страница 60: ...DIAS DRIVE 210 23 Page 60 30 03 2021 6 3 Dimensions ...
Страница 65: ...DIAS DRIVE 210 23 30 03 2021 Page 65 7 2 Mechanical Dimensions Integrated into the SDD3xx servo amplifier ...
Страница 79: ...DIAS DRIVE 210 23 30 03 2021 Page 79 ...
Страница 81: ...DIAS DRIVE 210 23 30 03 2021 Page 81 ...