C-DIAS SAFETY DIGITAL OUTPUT MODULE 

CSTO 082 

1.5 

Page 1 

 
Document changes and version status 
 

Change date

 

Affected 

page(s)

 

Changes/expansions/corrections

 

Version

 

19.12.2013 

12 to 12a 

Added Standard and Electrical requirements for UL table 

1.1 

17.02.2016 

11 

Switching-off inductive loads 

1.2 

15.05.2017 

12 

Specifications  of  maximum  allowable  output  loads  re-
fined 

1.3 

04.12.2017 

5, 8, 9, 14 

14 
 
 
 
 
15 

Removed standard IEC 61508 
Added amendments 

„Category 4“ and „EN“ 

Added chapter 

„Conformity with EU Standards” 

Added amendment 

„EN“ (62061) 

Added „Cat. 4“ 
Added unit 1/h on PFH

D

 value 

Changed value from 7.05 auf 7.05E-09 geändert 
Changed EMC resistance to 61000-6-2:2005 

1.4 

31.01.2018 

Note Safety outputs protected polarity changed 

1.5 

Содержание CSTO 082

Страница 1: ...hing off inductive loads 1 2 15 05 2017 12 Specifications of maximum allowable output loads re fined 1 3 04 12 2017 5 8 9 14 8 14 15 Removed standard IEC 61508 Added amendments Category 4 and EN Added...

Страница 2: ...5 The C DIAS bus and Connector Layout 6 Designated Use 9 Mechanical Dimensions 10 Technical Data 11 Output specifications 11 Maximum inductive load L mH at load current I A 12 Maximum capacitive load...

Страница 3: ...hanical dimensions 10 Fig 4 Inductive load 12 Fig 5 Capacitive load 12 Fig 6 CSTO 082 circuit 16 Fig 7 Connector plug coding 19 Fig 8 Simplified status diagram 20 Fig 9 Output circuit structure 22 Fig...

Страница 4: ...start up of individual modules or the entire Safety application the instructions and explanations in this documentation must be followed explicitly Delivery Condition The individual SIGMATEK Safety c...

Страница 5: ...ccording to EN 62061 Safety guidelines EMVG Function and operation To power the Safety modules correctly the C DIAS bus must be used see below The construction and structure are shown in the following...

Страница 6: ...5 5 CDIAS_ RD 5 CDIAS_ WR 6 6 CDIAS_A6 6 CDIAS_A7 7 7 CDIAS_A4 7 CDIAS_A5 8 8 CDIAS_A2 8 CDIAS_A3 9 9 CDIAS_A0 9 CDIAS_A1 10 10 CDIAS_D6 10 CDIAS_D7 11 11 CDIAS_D4 11 CDIAS_D5 12 12 CDIAS_D2 12 CDIAS...

Страница 7: ...ication be tween the Safety CPU and the design tool SafetyDesigner On the C IPC and coupler modules connectors are provided over which the C DIAS bus must be externally supplied with a voltage of 24 V...

Страница 8: ...afety output module CSTO 082 is suited for use in systems with optional modules and interface variables in accordance with the system hand book version 1 5 sections 1 6 7 1 and 7 2 To use the Safety o...

Страница 9: ...re people who have completed training or have been trained under supervision of qualified personnel and have been author ized to operate and maintain safety related equipment systems and facilities in...

Страница 10: ...CSTO 082 C DIAS SAFETY DIGITAL OUTPUT MODULE Page 10 31 01 2018 Mechanical Dimensions Fig 3 Mechanical dimensions...

Страница 11: ...current per channel 2 A Maximum total current per output group 2 outputs 2 A Maximum total current complete module 8 A up to a max 45 C ext temperature 6 A up to a max 50 C ext temperature 4 A up to a...

Страница 12: ...age 12 31 01 2018 Maximum inductive load L mH at load current I A Fig 4 Inductive load Maximum capacitive load C F at load current I A Fig 5 Capacitive load I A L mH C F 0 6400 1 25 0 5 1600 3 13 1 40...

Страница 13: ...upt time for volt age interruptions 10 ms Standard UL 508 E247993 Table 4 Electrical requirements Electrical requirements for UL IMPORTANT The device was tested in accordance with the UL 508 Norm as a...

Страница 14: ...65 EU RoHS Directive Functional safety standards EN IEC 62061 SIL 3 or SIL CL 3 EN ISO 13849 PL e Cat 4 Configuration 2 channel redundant diverse Safety parameters Diagnostic coverage DC 95 94 Probab...

Страница 15: ...061 Shock resistance EN 60068 2 27 15 g Protection Type EN 60529 IP 20 Table 6 Environmental conditions Miscellaneous Article number 12 892 082 Hardware version 1 x Table 7 Miscellaneous Output Power...

Страница 16: ...CSTO 082 C DIAS SAFETY DIGITAL OUTPUT MODULE Page 16 31 01 2018 CSTO 082 Circuit Fig 6 CSTO 082 circuit For the functions and LED display see the following chapter LED Displays...

Страница 17: ...he 24 V supply for outputs and clock signals are within the defined limits RN Green RUN Indicates the time unlimited LED ST off operational mode ST Yellow Status Lights permanently The module is curre...

Страница 18: ...et 3 connector plugs with spring terminals Phoenix Contact FK MCP 1 5 4 ST 3 5 is included in delivery of the C DIAS module TO1 group 1 X1 1 Digital output 1 TO2 group 1 X1 2 Digital output 2 TO3 grou...

Страница 19: ...ec tions A red coding pin is thereby placed in the socket Concurrently the protruding nose is removed from the corresponding pin in the plug The respective plug can therefore only be inserted into the...

Страница 20: ...osis based on the LEDs alone consult the corresponding chapter in the Safety System Handbook as well For an exact error analysis the SafetyDesigner must be used Restart Errors The following diagram sh...

Страница 21: ...will remain in the error status and must be restarted d A change to the error status can also occur from the POST and Temp OP mode if other internal errors are detected or errors in remote modules oc...

Страница 22: ...CSTO 082 C DIAS SAFETY DIGITAL OUTPUT MODULE Page 22 31 01 2018 Output Circuit Fig 9 Output circuit structure...

Страница 23: ...start button S1 should have a 2 channel connection R2 The signal lamp P1 should turn on immediately after pressing the start button S1 To activate the signal lamp P1 a safe output can be used R3 For...

Страница 24: ...ion and wired to 2 safe inputs The normally closed contacts of the Emergency Stop switch S2 are connected to the signal outputs A and B over 2 channels cross circuit detection and wired to 2 safe inpu...

Страница 25: ...012 Con nectors Pin Connection X2 1 Normally open start button S1 B 2 Normally open start button S1 B 3 Normally closed Emergency Stop S2 A 4 Normally closed Emergency Stop S2 b X3 1 Output A 2 Clock...

Страница 26: ...CSTO 082 C DIAS SAFETY DIGITAL OUTPUT MODULE Page 26 31 01 2018...