C-DIAS PROCESSOR MODULE
CCP 521
15.03.2016
Page 25
14
PROG MEMO
The CPU is currently programming the
memory module.
15
STOP BRKPT
The CPU was stopped by a breakpoint in
the program.
16
CPU STOP
The CPU was stopped by the PG soft-
ware (F6 HALT in status test).
17
INT ERROR
The CPU has triggered a false interrupt
and stopped the user program or has
encountered an unknown instruction
while running the program.
Cause:
-
A nonexistent operating system was
used.
-
Stack error (uneven number of PUSH
and POP instructions).
-
The user program was interrupted by a
software error.
Solution:
-
Correct programming error.
18
SINGLE
STEP
The CPU is in single step mode and is
waiting for further instructions.
19
Ready
A module or project has been sent to the
CPU and it is ready to run the program.
20
LOAD
The program has stopped and is receiv-
ing a module or project.
21
UNZUL.
Modul
The CPU has received a module, which
does not belong to the project.
22
MEMORY
FULL
The operating system memory /Heap) is
too small. No more memory could be
reserved, when an internal or interface
function was called from the application.
23
NOT LINKED
When starting the CPU, a missing
module or a module that does not belong
to the project was detected.
24
DIV BY 0
A division error has occurred.
Possible Causes:
-
Division by 0.
-
The result of a division does not fit in
the result register.
Solution:
-
Correct programming error.