11 Status and Error Messages
Status and error messages are displayed in the LASAL CLASS software status test.
Number
Message
Definition
Cause/solution
00
RUN RAM
The user program is currently running in
RAM.
The display is not affected.
Info…
01
RUN ROM
The user program stored in the program
memory module was loaded into the
RAM and is currently running.
The display is not affected.
Info
02
RUNTIME
The total time for all cyclic objects
exceeds the maximum time; the time
can be configured using 2 system
variables:
-
Runtime: Remaining time
-
SWRuntime: Preset value for runtime
counter
Solution:
-
Optimize the application's cyclic
task.
-
Use higher capacity CPU.
-
Configure preset value
03
POINTER
Incorrect program pointers were
detected before running the user
program
Possible Causes:
-
The program memory module is
missing, not programmed or
defective.
-
The program in the user program
memory (RAM) is not
executable.
-
The buffer battery has failed.
-
The user program has
overwritten a software error.
Solution:
-
Reprogram the memory module,
if the error reoccurs exchange
the module.
-
Exchange the buffering battery
-
Correct programming error
04
CHKSUM
An invalid checksum was detected
before running the user program.
Cause/solution: s. POINTER
Содержание 20-004-313
Страница 15: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 13...
Страница 17: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 15 5 Mechanical Dimensions...
Страница 30: ...CP 313 S DIAS CPU MODULE Page 28 29 05 2020 9 Wiring 9 1 Wiring Example...
Страница 33: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 31 10 Process Diagram...
Страница 56: ...CP 313 S DIAS CPU MODULE Page 54 29 05 2020...