CP 313
S-DIAS CPU MODULE
Page 12
29.05.2020
4.3
Electrical Requirements
4.3.1
Module Supply (Input)
Supply voltage
+18-30 V DC (SELV/PELV), typ24 V DC
UL: Class 2 or LVLC
(1)
Current consumption of +24 V
supply voltage
maximum 2.75 A
(2)
(1)
Limited Voltage/Limited Current
(2)
The current consumption is dependent on the connected load
When loading the internal capacitors, power consumption may be
increased for a short time (in the microsecond range).
This value is dependent on the input voltage and impedance of the power
source
(1)
For USA and Canada:
The supply must be limited to:
a) max. 5 A at voltages from 0-20 V DC, or
b) 100 W at voltages from 20-60 V DC
The limiting component (e.g. transformer, power supply or fuse) must be
certified by an NRTL (Nationally Recognized Testing Laboratory, e.g. UL.
4.3.2
S-DIAS Bus Supply (Output)
Voltage supply from S-DIAS bus
+5 V
Current consumption on the S-DIAS
bus (+5 V supply)
maximum 1.1
(1)
Voltage supply from S-DIAS bus
+24 V
Current consumption on the S-DIAS
bus (+24 V supply)
maximum 1,6 A
(1)
(1)
The current consumption is dependent on the connected load
Содержание 20-004-313
Страница 15: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 13...
Страница 17: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 15 5 Mechanical Dimensions...
Страница 30: ...CP 313 S DIAS CPU MODULE Page 28 29 05 2020 9 Wiring 9 1 Wiring Example...
Страница 33: ...S DIAS CPU MODULE CP 313 29 05 2020 Page 31 10 Process Diagram...
Страница 56: ...CP 313 S DIAS CPU MODULE Page 54 29 05 2020...