Install the ground lug provided
on either side of the panel as
shown. Tighten to 10-15 in.-lbs
(1.1-1.7 N-m).
Lock washer should be installed on nut
side of panel.
2
HD5
®
Screened Patch Panel Instructions
Place the screened HD5 Panel
(P/N: HD5-S) on sturdy surface
as close to rack as possible and remove
rear cover. If cable slack does not allow
this, mount to 19 inch relay rack or
equivalent with 12-24 screws and
washers, provided.
1
Route cables to point of
termination at the S110
®
connecting block and cut cables providing
extra length for termination
(approximately 5-10cm [2-4 in.] past the
S110 connecting block). Ensure that
enough slack is provided to properly
secure cables to rack or rear cable
manager if used.
3
For Cables With Foil Shield
Intact:
Fold foil shield back over jacket
(approximately 7.7cm [3 in.]).
Note: If braid exists, proceed to step 8.
Wrap drain wire (if present) around foil
shield within 1.3cm [.5 in.] of jacket end.
(Wrap drain wire a minimum of 3 times
around cable jacket).
6
For Cables With Foil Shield
Intact:
Insert or place cable between ground clip
and spade. Proceed to step 11.
7
Loosen screw retaining ground
clip enough to insert prepared
cable between ground clip and spade.
Note: Ground clip can be removed completely
to ease installation of cable.
4
Remove cable jacket
(approximately 7.7cm [3 in.]).
It is recommended to leave the foil intact
(as shown).
• If foil is intact see steps 5-6.
• If foil is removed see step 7.
• If the cable has a braid see steps
8-10.
5
For Braided Cables:
If foil exists beneath braid,
remove foil to point of jacket removal.
10
For Cables With The Foil
Removed:
If foil shield is removed during sheath
removal process, wrap drain wire (if
present) around sheath within 1.3cm [.5
in.] of jacket end. Push cable onto spade
of shield termination assembly. Proceed to
step 11.
Note: If plastic wrap exists between foil and
conductors, slide the cable onto the ground
spade and then remove plastic wrap.
8
For Braided Cables:
Note: If braid exists, fold braid back
over itself and wrap drain wire a minimum of 3
times around braid.
9
Spade
Screw
Ground Clip
Push
Grab
Slide braid
over itself
Drain Wire
Spade
OR