Class X (DCLC) Device Loop Card

Installation Instructions
Model XDLC

INTRODUCTION

The Model XDLC Device Loop Card from Siemens Industry,
Inc., is the interface for connection of Desigo Fire Safety
Modular/Cerberus PRO Modular smoke detectors, Multi-
Criteria detectors including Carbon Monoxide, manual
stations, monitor devices, and control devices to the Desigo
Fire Safety Modular/Cerberus PRO Modular System. The
XDLC uses one network address on the system. The
application program that is loaded into the on-board micro-
processor controls the XDLC operation.

The XDLC contains 16 LEDs for diagnosis of problems.
Ground fault detection is provided by the loop.

All field devices connected to the XDLC are addressed and
tested using the Device Programming Unit (DPU).

OPERATION

The XDLC initializes, operates, and maintains all devices
residing on the loop. The XDLC communicates all relevant
device and event information, such as alarms and troubles,
to the PMI-2/PMI-3/OI-C/OI-D (PMI). The sensitivity of any
intelligent smoke detector can be checked and adjusted
from the PMI through the XDLC. All information about the
devices on the loop can be displayed on the PMI. The XDLC
allows the System polarity insensitive devices to be
connected without generating errors.

NOTE:

 PMI = PMI-2/PMI-3/FCM2041

The XDLC supports four Class A (DCLA) or Class X (DCLC)
loops (eight Class B [DCLB] parallel lines/stubs) of up to
252 Desigo Fire Safety Modular/Cerberus PRO Modular
intelligent field devices as well as device accessories (relay
bases, audible bases, and remote lamps) in any combina-
tion. The microprocessor controls the on-board isolators to
isolate any zone from the loop if one of them is shorted.
When one zone is isolated from the loop, the other zones
will still work.

The on-board microprocessor provides the XDLC with the
ability to function and initiate alarm conditions even if the
main PMI CPU fails. The XDLC accomplishes this “degrade” mode of operation by
monitoring the communications with the PMI. In the case of the failure of the PMI,

XDLC

RESET

CARD FAIL

GND FAULT

TROUBLE

OPEN
SHORT

ZONE 1

USB

HUNDREDS

TENS

ONES

HNET

POWER

HNET FAIL

ALARM

1

2

ZONE 2

ZONE 3

ZONE 4

3

4
5

6

7

8

Figure 1

XDLC Device Loop Card

Содержание XDLC

Страница 1: ...DLC communicates all relevant device and event information such as alarms and troubles to the PMI 2 PMI 3 OI C OI D PMI The sensitivity of any intelligent smoke detector can be checked and adjusted from the PMI through the XDLC All information about the devices on the loop can be displayed on the PMI The XDLC allows the System polarity insensitive devices to be connected without generating errors ...

Страница 2: ...ed indi cates the power for the XDLC is applied to the card Blinks during firmware download or if download has failed CARD FAIL Yellow Normally OFF When illuminated indi cates the card microprocessor has failed HNET Yellow Normally OFF When illuminated indi cates that the HNET communication with the XDLC has terminated and the card goes into degrade mode on HNET failure GND FAULT Yellow Normally O...

Страница 3: ... standard USB A B cable connected to a PC running Zeus a new XDLC Firmware can be downloaded The Zeus Configuration Program is used to select the new Firmware and initiate the download to the XDLC Both the power LED and the Ground Fault LED will blink during download The power LED will blink alone if the firmware was not completely downloaded to the XDLC In addition to Firmware Download the USB po...

Страница 4: ...ng it counterclockwise 2 Insert the wire into the side of the terminal block 3 Tighten the screw of the terminal block by turning it clockwise Connect 24V from the PSC 12 to terminal 17 and 24V from the PSC 12 to terminal 18 of the slot in the CC 5 where the XDLC will be installed Refer to Figure 3 LINE 1 OUT LINE 1 OUT LINE 1 RETURN LINE 1 RETURN LINE 2 RETURN LINE 2 RETURN LINE 2 OUT LINE 2 OUT ...

Страница 5: ... END ONLY TERMINATE TO EARTH GROUND CLASS B WIRING T TAPPING ALLOWED ZONE 1 1 INITIATING DEVICE ZONE 2 3 SHIELD OPTIONAL TERMINATE IN ENCLOSURE WITH THE XDLC TERMINATE AT ONE END ONLY TERMINATE TO EARTH GROUND LINE 2 OUT 9 10 11 12 13 14 15 16 OPERATES IN FULL CONFORMANCE WITH CLASS A ULC DCLA 1 2 3 4 5 6 7 8 ZONE 1 INITIATING DEVICE CC 5 LINE 1 RETURN LINE 1 RETURN LINE 1 OUT LINE 1 OUT ZONE 2 LI...

Страница 6: ...L2572 Use any combination of those listed inTable 1 orTable 2 as applicable 2 The XDLC supports a maximum of 252 Desigo Fire Safety Modular Cerberus PRO Modular intelligent field devices distributed across four Class A DCLA loops or eight Class B DCLB loops A mix of Class A DCLA and Class B DCLB is supported The XDLC supports a maximum of 190 Desigo Fire Safety Modular Cerberus PRO Modular intelli...

Страница 7: ... 4 0 5 1 3 N P 5 7 4 9 4 0 5 1 3 N P 0 5 8 4 3 0 5 1 3 N P 7 3 6 8 4 0 5 1 3 N P 7 3 6 8 4 0 5 1 3 N P 4 8 4 5 5 0 1 0 1 V 6 A 4 8 4 5 5 0 1 0 1 V 6 A 6 3 9 3 2 3 0 1 V 6 A 9 5 6 4 2 3 0 1 V 6 A 1 6 6 4 2 3 0 1 V 6 A 8 2 9 3 2 3 0 1 V 6 A 8 5 3 0 3 0 1 0 1 V 6 A 6 6 3 0 3 0 1 0 1 V 6 A 9 5 3 0 3 0 1 0 1 V 6 A 0 3 2 3 3 0 5 1 3 N P 0 3 2 3 3 0 5 1 3 N P 8 2 4 3 8 3 0 1 V 6 A 6 8 4 5 5 0 1 0 1 V 6 A...

Страница 8: ... 3 0 1 0 1 V 6 A 6 6 3 0 3 0 1 0 1 V 6 A 9 5 3 0 3 0 1 0 1 V 6 A 6 8 4 5 5 0 1 0 1 V 6 A 9 7 4 5 5 0 1 0 1 V 6 A 7 8 4 5 5 0 1 0 1 V 6 A 9 7 4 5 5 0 1 0 1 V 6 A 9 7 4 5 5 0 1 0 1 V 6 A o N o N o N o N o N o N o N o N o N o N o N o N o N o N o N o N P P P P P P P I P I I I I P I P I P I P I P I e c i v e D e v i t i s n e s n I y t i r a l o P P e c i v e D e l b a p a C e d o M r o t a l o s I I r...

Страница 9: ...s Isolators CLASS A Mixed Mode P Device s Polarity Insensitive Max 20 Devices between Isolators I Isolator Device s Wired for Isolator Mode PANEL XDLC Out Return PANEL XDLC Out P P P P P P P CLASS X I Isolator Device s All wired for Isolator Mode CLASS B P Device s Polarity Insensitive No Devices used as Isolators I I I I I I I I I I I Figure 5 Class A Device Loop Topologies Figure 6 Class X and B...

Страница 10: ...ensive state of the art security concept that is customized to individual security needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protect...

Отзывы: