Wireless Room Sensor Solution
Appendix B–Powering RSX Using 9 Vdc Battery
This appendix provides steps for using a 9 Vdc battery to temporarily power the RSX. This is helpful during
site survey situations where RSXs can be easily placed at various locations in a building. While the RSX is
designed to run primarily using 24 Vac power, a 9 Vdc battery can also be used to provide temporarily
power. When powered from a 9 Vdc battery, an RSX runs for approximately 4 to 6 hours.
Follow these steps to power the RSX using a 9 Vdc battery:
1. Create a cable using appropriate wires and connectors to connect the 9 Vdc battery to RSX as follows:
•
Connect the positive (+) battery terminal to the “H” terminal on the RSX 24 Vac power connector.
•
Connect the negative (-) battery terminal to the “N” terminal on the RSX 24 Vac power connector.
Figure 10. Connecting a 9 Vdc Battery to RSX.
You can obtain 9 Vdc battery snap connectors with red (+) and black (-) leads from an electronics
store (such as those sold by Radio Shack
—
part number 270–324).
2. Connect the cable to the 9 Vdc battery and 24 Vac power connector on the RSX.
Revision Date: July 10, 2008
39
Siemens Building Technologies, Inc.