Installation Instructions

Document No. 563-201

March 12, 2008

 

WFLN Series 

Wireless Field Level Network Transceiver (FLNX) 

(Version 2.x)

 

 

Item Number 563-201, Rev. CA

 

Page 1 of 5

 

 

Figure 1. Wireless Field Level Network 

Transceiver. 

Product Description 

The Wireless Field Level Network Transceiver 
(FLNX) is mounted at or near the FLN device and is 
powered by 24 Vac. The antenna can be mounted 
directly to the radio or mounted remotely for 
installations where the location of the FLNX causes 
the antenna to be shielded—for example, when the 
FLNX is mounted inside a TEC enclosure. 

Product Numbers 

563-054 

Wireless Field Level Network 
Transceiver (FLNX) with WRTS 
Support (Version 2.x) 

563-007 

Direct Mount Antenna 

563-008 

Remote Mount Antenna 
 

 

Transceivers do not come with antennas. 
Antennas must be ordered separately. 

 

Accessories 

563-027 

Pre-terminated Cable Kit 
Includes two 14 in. (36 cm) cables: 
– Power 
– Communication 
Recommended for factory mounting. 

Related Products 

Wireless Field Level Network (WFLN) 

563-055 

Wireless Field Panel 
Transceiver (FPX) 

563-056 

Wireless Transceiver Tool (TLX) 

QAA2290.EWSC  Wireless TEC Room 

Temperature Sensor (WRTS) – 
Sensing only 

QAA2290.DWSC  Wireless TEC Room 

Temperature Sensor (WRTS) – 
Sensing with Temperature 
Display 

QAA2290.FWSC 

Wireless TEC Room 
Temperature Sensor (WRTS) – 
Sensing with Override, Setpoint, 
and Temperature Display 

 

Warning/Caution Notations 

CAUTION: 

 

Equipment damage, or loss of 
data may occur if you do not 
follow the procedures as 
specified. 

 

Expected Installation Time 

10 minutes 

Required Tools and Materials 

 

Electro-static discharge wrist strap 

 

Small flat-blade screwdriver 

 Cordless 

drill/driver 

set 

Содержание WFLN Series

Страница 1: ...te Mount Antenna Transceivers do not come with antennas Antennas must be ordered separately Accessories 563 027 Pre terminated Cable Kit Includes two 14 in 36 cm cables Power Communication Recommended for factory mounting Related Products Wireless Field Level Network WFLN 563 055 Wireless Field Panel Transceiver FPX 563 056 Wireless Transceiver Tool TLX QAA2290 EWSC Wireless TEC Room Temperature S...

Страница 2: ... preferred mounting configuration is to mount the FLNX outside the TEC enclosure in a location where it will establish the maximum number of communication links with other FLNXs and its associated FPX For example in a VAV application this is typically on the bottom of the VAV box in the ceiling plenum with the entire antenna extending downwards below the VAV box Figure 2 Remote Mount Antenna The F...

Страница 3: ...C Transceiver TTX P N 550 205 and the TEC be sure to use a ground isolated transformer P N 550 710 between the TTX and the power transformer 24 V AC C E H C H DO 1 DO 2 DO 3 DO 4 DO 5 NO C NO C NO C NO C NO C DO 6 DI 3 DI 2 FLN TRUNK NO C AI 3 TX RX S BST RTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 WLAN0072R2 TEC Power From Transformer TEC Typical Channel Netw...

Страница 4: ... the antenna base not the antenna itself so the antenna can be adjusted c Connect the antenna wire securely to the FLNX 7 Position the antenna in a vertical orientation up or down The installation is complete To temporarily power an FLNX such as for a site survey or determining the best placement for an FLNX used as a repeater you can use a common 9V battery Use a battery snap connector available ...

Страница 5: ...ccur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an ...