UTMC OTU/MOVA Handbook
667/HB/31601/000
Page 44
Issue 5
6.2.5 SCOOT Detector Mapping via Controller Serial Link
The controller can be configured to pass SCOOT detectors to the OTU via the serial
link. This is configured on the IC4 “serial MOVA/UTC” screen. It is recommended that
SCOOT loop 1 is allocated to detector 64, SCOOT loop 2 is allocated to detector 63,
etc to avoid clashing with MOVA detectors, which are allocated from 1 upward.
2. Modify the detector bit
numbers to match the detector
allocations on the IC4 “Serial
MOVA” screen.
3. SCOOT detectors are
routed via the controller using
port “csi.det.in.1”.
1. Select the SCOOT
detector site to edit.
4. Use "Submit" to save the changes to
the screen and then when all changes
completed use “Save to File”.