6 Updates
6.1
Firmware Update
6.1.1
FW Upload to TX-I/O BIM
1
2
Extract the file pnbim_fw_V0_2_xx.bin and copy it together with the GSDML
file to a local folder – e.g., C:\temp.
Passwords are required below during the login procedure.
User name
Password
Rights
guest
guest01
Read rights (monitoring)
user user01
Firmware
configuration updates and monitoring
root root All
rights
1
Start > Run
2
Enter cmd in the text box and then return key
Opens the DOS commander
3
Optional (recommended): navigate to the folder named above (e.g., C:\temp)
with cd c:\temp > return key
4
At the DOS prompt (C:\temp>) enter: ftp > return key
Prompts ftp>
5
At the DOS prompt (ftp>) enter the IP address of the TX-I/O BIM:
open xxx.xxx.xxx.xxx
>
return key
Displays 'Connected to <IP address> and 220 Service ready'
6
At the DOS prompt User (<IP address>: (none)) enter: user > return key
Display '331 User name ok, need password'
7
At the DOS prompt (password:) enter (hidden text input): user01 > return key
Displays '230 User logged in'
8
At the DOS prompt (ftp>) enter:
put pnbim_fw_Vx_x_xx.bin > return key
Displays '200 Command OK, 150 Connecting for STOR, 226 Transfer OK,
Closing connection' and 'ftp: xxxxxx bytes sent in xxx.xx Seconds
xx.xxKbytes/s.'
9
At the DOS prompt (ftp>) enter: quit > return key
Exits ftp
Preparation
Passwords
Step-by-step procedure
Содержание TX-I/O
Страница 1: ...s TX I O TX I O PROFINET BIM V1 0 User manual CM110564en_02 23 09 2010 Building Technologies ...
Страница 90: ...90 94 Siemens TX I O PROFINET BIM V1 0 CM110564en_02 Building Technologies Hardware 23 09 2010 ...
Страница 93: ...93 94 Siemens TX I O PROFINET BIM V1 0 CM110564en_02 Building Technologies Index 23 09 2010 ...