51 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Parameters
23.09.2010
0
0
°C
1
0.1 °C
1000
100.0 °C
5000
50.00 °C
5001
5250
52.50 °C
Underflow range
Lower limit range
32513
80FF
32768
8000
<
52.50 °C
Underflow
SIMATIC value
Analog value
Description
Decimal
Hex
32767 7FFF >256
/ 2.56 k
26500 7F00
Overflow
26499
256
/ 2.56 k
25001
Upper limit range
Overshoot range
25000
250
/ 2.5 k
10000
100
/ 1 k
1 0.01
/ 0.1
0 0
Rated range
4.10.5 Channel Diagnosis
Alarm type
Cause / solution
Invalid
Check the module configuration and parameterization
No_Output
Operating voltage too low ->
check the power
Over_Range
Sensor shows a higher value than the rated range
> check the sensor output
Under_Range
Sensor shows a lower value than the rated range
> check the sensor output
Short_Loop
The connection between the sensor and module shows a value that indicates a
short-circuit > check the sensor and cable connection between the sensor
and module
Open_Loop
The connection between the sensor and module shows a value that indicates an
interruption > check the sensor and cable connection between the sensor
and module
No_Sensor
The 4...20 mA current measurement signal indicates the value
No_Sensor
if no
current was measured.
> check the sensor and cable connection between the sensor and module
Unreliable
The operating voltage ACDC 24 V is below a specific value (AC or DC) > check the
operating voltage value (power supply)
Function
Short loop
Under range
Over r
ange
Open loop
No sensor
Unreliable other
V
ACDC
o
r V
DC
AI_U10N
X X X X
AI_I020
X X X X
AI_I420N
X X X X
AI_NI1K
X X X X
AI_PT1K375
X X X X
AI_PT1K385
X X X X
AI_R2K5
X X
AI_T1
X X X X
AI_NTC10K
X
X
X
Resistance
measurement
Error messages
(overview)
Содержание TX-I/O
Страница 1: ...s TX I O TX I O PROFINET BIM V1 0 User manual CM110564en_02 23 09 2010 Building Technologies ...
Страница 90: ...90 94 Siemens TX I O PROFINET BIM V1 0 CM110564en_02 Building Technologies Hardware 23 09 2010 ...
Страница 93: ...93 94 Siemens TX I O PROFINET BIM V1 0 CM110564en_02 Building Technologies Index 23 09 2010 ...