Configuration
4.13 Communication with the CPU
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
81
3.
Click the "Import partner configuration" button.
Figure 4-4
Importing the configuration data
The dialog for selecting the file with the configuration data opens
4.
From the file system of the engineering station open the text file that you exported from
the proxy from the STEP 7 V5 project.
Figure 4-5
Selection of the file "sdbs_xxx.txt" with the configuration data from STEP 7 V5.
You can see the result of the import of partner data in the table "Partner stations".
In the "Imported configuration data file" output field, the file name of the imported SDBs is
displayed.
With the "Reset partner configuration" button you can delete the imported data again. The
partner-specific configuration data are then deleted.
Table "Partner stations"
This is where the data on the imported partner data is shown.
4.13
Communication with the CPU
Communication with the CPU
Using the first three parameters you specify the CPU access by the TIM in the CPU scan
cycle. You will find the structure of the CPU scan cycle in the section Read cycle (Page 115).
The fourth parameter "Frame memory size" decides the size of the send buffer of the TIM for
frames of data points that are configured as an event.
●
Cycle idle time
Wait time between two scan cycles of the CPU memory area
●
Max. number of write jobs
Maximum number of write jobs to the CPU memory area within a CPU scan cycle
Содержание TIM 1531 IRC
Страница 262: ...Block library TeleControl ST7 5 7 Master copies TIM 1531 IRC 262 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 302: ...Dimension drawings TIM 1531 IRC 302 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 322: ...Documentation references 13 TIM 1531 IRC 322 Operating Instructions 02 2018 C79000 G8976 C468 02 ...
Страница 336: ...Glossary TIM 1531 IRC 336 Operating Instructions 02 2018 C79000 G8976 C468 02 ...