Siemens TBM-2 Скачать руководство пользователя страница 1

P/N 315-093782-9

INTRODUCTION

The Model TBM-2 Termination Block module
from Siemens Industry, Inc., is the central
connection point for audio functions in the
MXLV System (See Figure 1). The ACM-1
Audio Control module communicates with
other modules in the system through the
TBM-2. In addition, the TBM-2 has connections
for the recording of telephone and microphone
messages, and the control connections to
activate recording equipment. Refer to the

CSG-M Manual,

 P/N 315-090381, to select

the Voice Options for your system.

The TBM-2 has two single pole, double throw
(SPDT) dry contacts, AUX CTRL1 and AUX
CTRL2, that control recording equipment.
When the microphone or telephone is active,
the signal goes to the chosen auxiliary output
and the corresponding control output changes
state. The TBM-2 does not include connectors
or cables for connecting the auxiliary outputs
and auxiliary controls.

The TBM-2 has a connection for an external
signal source. Use the AUX IN input and a
VSM-1 function to connect an external signal
source to the MXLV System. See Figure 4 for
information on input signals.

The TBM-2 provides screw terminal blocks
and connectors that interface the internal
wiring and field wiring (See Table 1).

For additional information on the MXL/MXLV
System, refer to the 

MXL/MXLV Manual, P/N

315-092036.

INSTALLATION

Remove all system power before installation,
first battery and then AC. 

(To power up, connect

the AC first and then the battery.)

The TBM-2 mounts on the right side of the
backbox next to the MMB or PSR-1, approxi-
mately one-third of the way down from the top
(Refer to Figure 2).

NOTE:

In a Remote Extender enclosure the
TBM-2 mounts below the PS-5N7. Refer
to the 

PS-5N7 Instructions,

 P/N 315-092729.

Installation Instructions

Model TBM-2
Termination Block Module

TABLE 1

TBM-2 CONNECTIONS

Connector

Connects

  TB2

Digital Message Unit audio signal
connection

  TB5

Supervised riser signals to System
(Style Y or Z)

  TB4

Supervised telephone riser signal
(Style Y)

  P1

SPDT contact to start the recorder for
AUX OUT 1

  P2, P3

Plug-in cable power connections for
ACM-1

  P4

Plug-in cable power connection for
VSM-1/VLM-1/VFM-1

  P5

Plug-in cable power connections for
TMM-1

  P6

SPDT contact to start the recorder for
AUX OUT 2

  J1

AUX IN RCA type jack

  J2

AUX OUT 1 RCA type jack

  J3

AUX OUT 2 RCA type jack

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada

Содержание TBM-2

Страница 1: ...ctors that interface the internal wiring and field wiring See Table 1 For additional information on the MXL MXLV System refer to the MXL MXLV Manual P N 315 092036 INSTALLATION Remove all system power before installation first battery and then AC To power up connect the AC first and then the battery The TBM 2 mounts on the right side of the backbox next to the MMB or PSR 1 approxi mately one third...

Страница 2: ...onnec tions Connect terminals 1 and 4 in one cable going out to Riser 1 Connect terminals 2 and 3 in another cable coming back from the last destination of Riser 1 The other audio risers connect in a similar fashion For Style Y connections use only one cable Refer to Figure 3 for details Figure 1 TBM 2 Termination Block Module Figure 2 Mounting the TBM 2 NOTE In a Remote Extender enclosure a PS 5N...

Страница 3: ...ISER 1 AUDIO RISER 2 AUDIO RISER 3 CONNECTION AT FIRST OCC 1 TERMINAL BLOCK CONNECTION AT SECOND OCC 1 TERMINAL BLOCK CONNECTION AT LAST OCC 1 TERMINAL BLOCK INCLUDES EOL STYLE Y STYLE Z NOT USED TERMINATED For Style Z connections the lines connected to terminals 1 and 4 are in one cable The lines connected to terminals 2 and 3 are in another cable Connect the shield from the cable connected to te...

Страница 4: ...The signal source must have isolation using a transformer 5 The load impedance for AUX OUT must not be less than 10K ohms 200mV RMS 6 The load must have isolation using a transformer 7 SPDT contacts activate when audio is present on AUX OUT jacks based on the CSG M selection of microphone or tele phone Contact ratings 0 3A at 24 VDC If AUX OUT 1 is microphone then AUX OUT 2 is telephone If AUX OUT...

Отзывы: