5.5
Data transfer control unit <−> SWE330A
Proceed as shown below.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
FUNCTIONS: 1. function
(4) 2. system TEST
3. printout
4. configuration
CONFIGURATION: 1. user functions
(4.4) 2. user text
3. service functions
4. erase functions
Press «Start/stop» key and enter the password (0055 ok)
and proceed as follows
(Code 8642 ok )
SERVICE LEVEL: system configuration
> password?
hm: back to menu Stop: end operating
CONFIGURATION: 1. system data
(4.4.1) 2. collective line
3. password
4. addressable line
5. SWE330A
6. LON devices
7. serial ports
8. K6 inputs
enter 5 or select ’5.’ with arrow key
SWE TOOL active on port: ###### 1. NO
Select? 2. YES
– option ’2.’ YES = ready to communicate with SWE
– enter ’2.’ to set control unit to mode data transfer
– enter ’1.’ after data transfer is completed (timeout ...min.)
The connection is established if state ’connected....’ is indicated on the PC (SWE330A). Proceed by open