Parameterize OZW775
22.06.2012
Command sequence: Settings > System report
Data point
Explanation, example
Next report
Default val: 0
Setting val: 0…255 d (days)
See Section 5.4.5 on "Next report (system
report)".
Command sequence: Settings > Faults
Data point
Explanation, example
Delete history
Default val: No
Setting val: Yes
See Section 5.5.3 on "Delete history".
Note: Setting value "Yes" is a temporary state,
i.e. the setting value automatically goes to "No"
after ca. 2 seconds.
Command sequence: Settings > Text
Data point
Explanation, example
Reset text
Default val: No
Setting val: Yes
Setting value "Yes" resets the menu and fault
texts, i.e. to the default texts delivered with the
central communication unit.
Setting value "Yes" is a temporary state, i.e. the
setting value automatically goes to "No" after ca.
2 seconds.
Note: Customized texts for data points "Name"
and "Phone number" are not overwritten.
4.7.3 Data points in the "Device information" operating page
Command sequence: Device information > Central comm unit
Data point
Explanation, example
Central comm unit type
Default val: OZW775
Setting val: Read-only
The data point is read-only.
–
Software version (firmware)
Default val: 2.02
Setting val: Read-only
The data point is read-only.
Note: If you use the central communication unit
as a web server, you must load software version
(firmware) V2.02 or higher.
–
Hardware version
Default val: 1.00
Setting val: Read-only
The data point is read-only.
–
System report
Faults
Texts
Central communication
unit