Function settings
05.07.2007
Heating
Enable setpoint limitation
This defines whether setpoint limitation of the room temperatures is
basically be disabled or enabled. Only when setpoint limitation is
enabled does the central apartment unit respond to the setpoint limi-
tation signals received over the wire-bound bus.
Main menu > Heating > Apartment > Settings > Setpoint limitation:
Factory setting
Enabled
Your setting
Disabled
Enabled
Limitation setpoint
This defines the maximum permissible room temperature setpoint
(0..35 °C) during the period of time a setpoint limitation is transmitted
over the wire-bound bus.
Main menu > Heating > Apartment > Settings > Limitation setpoint:
Factory setting
25 °C
Your setting
Pump overrun time
The overrun time for the apartment pump and the DHW pump can be
set (0..30 min).
Main menu > Heating > Apartment > Settings > Pump overrun:
Factory setting
6 min
Your setting
Valve override
Valve override enables all valves of the apartment to be jointly driven
to the required valve position (0..100 %, e.g. for hydraulic balancing).
Main menu > Heating > Apartment > Settings > Valve override:
Guide value
--- (off)
Your setting
Valve override must be manually switched off again.
Otherwise, room temperature control stays deactivated. During
the period of time valve override is active, status message
”Valve override active“ is displayed.
Содержание Synco 900
Страница 1: ...Synco 900 Mounting and commissioning Edition 2 0 Controller series B CE1C2707en 05 07 2007 ...
Страница 2: ......
Страница 84: ...84 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 85: ...85 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 86: ...86 88 Siemens Synco 900 CE1C2707en Building Technologies 05 07 2007 ...
Страница 87: ......