3 Commissioning
05.02.2007
Main menu > Commissioning > Wiring test > Heating circuit 1
(or
2
or
3
)
> Outputs
Operating line
Positions
Heating circuit pump
Off / On
3.5
Completing commissioning
If the application is valid, the
Commissioning
menu can be quit as follows:
1. Press the ESC button. The display shows a menu with the following information:
Caution!
Plant starts
ESC
OK
2. Confirm by pressing the OK knob. Then, the controller starts with the settings
made; the plant is started up, and the Main menu appears on the display.
Main menu:
Commissioning
Heating circuit 1
Heating circuit 2
Heating circuit 2
3.6
Data backup
When commissioning is completed, the entire commissioning data set (configuration
and all settings) can be saved in the controller. If any time later, an unauthorized per-
son readjusts important values, this function can be used to restore the correct con-
trolled state after commissioning.
Main menu > Data backup
Operating line
Adjustable values / display / remarks
Storage date
Display of the date on which the commis-
sioning data set was downloaded to the
controller’s memory
Storage year
Display of the year in which the commission-
ing date set was downloaded to the control-
ler’s memory
Main menu > Data backup
Operating line
Adjustable values / display / remarks
Restore Caution!
New configuration
Save Caution!
Stored data will be overwritten.
Displays
Setting