You can change the following texts ex-works texts in the RMS705B at the
password level.
No. Text
Effect
1318
[Mot 1] precom no checkb signal
Urgent message; must be
acknowledged and reset.
1328
[Mot 2] precom no checkb signal
Urgent message; must be
acknowledged and reset.
1338
[Mot 3] precom no checkb signal
Urgent message; must be
acknowledged and reset.
1348
[Mot 4] precom no checkb signal
Urgent message; must be
acknowledged and reset.
1358
[Mot 5] precom no checkb signal
Urgent message; must be
acknowledged and reset.
1368
[Mot 6] precom no checkb signal
Urgent message; must be
acknowledged and reset.
Fault messages
8.4.10 Motor operating state
The output motor operating state indicates if the motor is running at full speed.
Set the time the motor needs to reach full speed via the run-up time.
Main menu > Commissioning > Settings >
…
or
Settings
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Runup time
00.00…59.59 m.s
00.10 m.s
You can configure the output motor operating state for all internal inputs.
Use the motor operating state e.g. to send a checkback signal of the motor
state to the rotary step switch.
The signal can have value "On"
or
"Off". It is "On" after the run-up time expires.
TiRup
Off
On
Function diagram
based on
1-speed motor
TiRup = Runup time
119 / 216