10.2 Connection terminals
G
G0
51
46
G
01
X1 M
X2 M G1
X3 M
X4 M G1
X5 M
Y2
G0
G1
Y1
G0
G1
G, G0
Rated voltage AC 24 V.
Key
G1
Power supply AC 24 V for active sensors or signal sources.
M
Measuring neutral for signal input.
G0
System ground for signal output.
X1…X5
Universal signal inputs (analog signals only)
for LG-Ni 1000, 2x LG-Ni 1000, T1, Pt 1000, DC 0…10 V, 0…1000
Ω
.
Y1, Y2
Measured value or control outputs, analog DC 0…10 V.
36 / 46
Siemens
SEZ220 signal converter
CE1P5146en
Building Technologies
Electrical connections