Engineer Programming Via the Keypad
79
Siemens Building Technologies
Fire Safety & Security Products
09.2008
Zone Status
Abbreviation
CLOSED CL
OPEN OP
SHORT SH
DISCONNECTED DIs
Tab. 23
Status Information
All zones on a system can be monitored for correct operation by performing a
monitoring test.
To perform a zone monitoring test:
1.
Scroll to the FULL ENGINEER> TEST> ZONE MONITOR programming
option.
2.
Press SELECT.
3.
Scroll to a preferred zone and press SELECT, or enter the zone number
directly.
Î
If the zone is located close to the Keypad, the status of the Keypad can be
viewed as it changes. The Zone status and resistance value displays on the
top right.
4.
Change the state of the sensor; e.g. for a door contact sensor, open the door.
Î
The Keypad buzzer beeps and the status of the sensor changes from CL
(Closed) to OP (Open). The corresponding resistance value changes to a
value that depends on the EOL resistance scheme.
NOTE
It is advisable to check the operation of all zones on the system after installation is complete. To locate
the zone select NEXT (bottom right) on the Keypad. A zone status value of SH or DI indicates that the
zone is shorted or disconnected.
10.12.4 Output Test
To perform an output test:
1.
Scroll to the OUTPUT TEST programming option.
2.
Press SELECT.
3.
Toggle between CONTROLLER and EXPANDER for preferred option.
4.
If testing the controller outputs, scroll to the preferred output and press
SELECT. If testing the Expander outputs, select the Expander and then the
output.
Î
The Keypad display indicates the current state of the output on the top line.
5.
Toggle the output state ON/OFF. Check that the device connected to the
selected output changes state accordingly.