Wiring the System
30
Siemens Building Technologies
Fire Safety & Security Products
09.2008
7.4
Wiring the Zone Inputs
The SPC Controller has eight on-board zone inputs. By default these inputs are
monitored using End of Line supervision. The installer can choose from:
z
NEOL
z
SEOL
z
DEOL
z
Anti-masking PIR
1
Input 1
4
Alarm
2
COM
5
Resistor
3
Tamper
6
4K7 EOL
Fig. 11
Default Configuration (DEOL 4K7)
1
Input 2
5
Alarm
2
COM
6
Anti-masking
3
Tamper
7
2K2
4
1K
8
EOL IK
Fig. 12
Anti-Masking PIR Configuration
Anti-Masking is only reported as "Alarm" type to ARC and if area or system is set.